Programming
1. Create the user program of the tdm R 360 by means of the editor ecolog tdm
R 360 (order no. CP9005). In addition to the operator and visualisation menus it
also contains the data to configure the CAN interface.
2. Remove the clamp cover of the tdm R 360 and connect it with the PC via the ser-
ial interface (RS232) or via the CANinterface. The connection cable is available as
an accessory (order no. EC2020).
3. Load the user program into the memory of the tdm R 360 (by means of the cor-
responding editor menu).
If necessary, the operating system (TOS) can also be loaded via the editor. It is sup-
plied with the editor.
TOS and program updates can be loaded at any time.
If there are problems with the data transfer proceed as follows:
- Configure the serial interface via the editor as follows: 9600 baud - 8 data bits - 2 stop bits
no parity.
- Disconnect the tdm R 360.
- Press 4 of the keys simultaneously, hold them down and reconnect the module.
The module displays "TERMINAL READY FOR UPLOAD". The software can now be transferred.
5. Labelling the function keys
1. Make a paper strip (for dimensions see page 8) and label it according to the
dimensions.
2. Attach its ends onto the supplied plastic strip.
3. Then insert it between the keys and front foil.
6. Mounting
1. Cut 187 x 120 mm out of the control
panel (3), debur and degrease it.
2. Glue the washer (2) to the front of
the control panell (3).
3. Loosen the two wing screws (5) and
remove the clamp cover (4) of the
tdm R 360.
4. Insert the unit (1) into the control
panel (3).
5. Place the clamp cover (4). Tighten the
two wing screws (5) alternately. The
display is then dust-tight and jet-
proof to IP65 from the front.