Product Information / Produktinformation A6125
Bearing Vibration Monitor
1.6.5 Power supply
The monitor system voltages, and thus the 0 V / common connections for the measurement
and monitoring inputs and outputs, are galvanically separated.
Supply voltage inputs
Voltage input UB+ / UN+
Common reference 0 V U−
Perm. voltage range
Power consumption
Monitor system voltage
The system voltages required for the internal supply are constantly monitored on overvoltage.
If undervoltage is detected an error message is generated.
Sensor supply
For both channels of the monitor
Separation
Sensor supply channel 1
Sensor supply channel 2
Current setting
Tolerance
Two redundant, diode decoupled inputs for nominal
+24 V with common 0 V reference
d2 / z2
b2
19 ... 31.2Vdc (IEC 654−2 class DC 4)
CSA: 24Vdc; SELV LPS
max. 6 W, at 24 V max. 250 mA
Decoupled and galvanically separated from the
supply voltage,
can be operated in parallel with other monitors, open
circuit and short circuit proof, non reactive.
SENS1− / SENS1+
b6/z6
SENS2− / SENS2+
b8/d6
2...8 mA, configurable in steps of 40 μA
±0,5 % of f.s.d, +0,5 % of the adjusted value
max. burden
3,4 kΩ at 8 mA,
13,6 kΩ at 2 mA
open−circuit and short−circuit proof
Page 19