Parallel cable loss
Alarm Code: E2
Parallel system
battery status
Alarm Code: E6
Line input different
Alarm Code: E7
Bypass input different
Alarm Code: E8
Power strategy
different
Alarm Code: E9
Rate power different
Alarm Code: EA
HE in parallel
Alarm Code: EB
56
In parallel system,
parallel cable disconnect
UPS1 connect battery,
UPS2 without battery
Parallel system,UPS1
line ok,UPS2 line loss
Parallel system,UPS1
bypass ok,UPS2 Bypass
loss
Parallel system,UPS OP
mode(normal ,
converter,HE) different
Parallel system rate
power different
Parallel system,OP
mode set as HE
Disconnect parallel cable
one turn to fault mode
Check battery connect
status
Check the line input
Bypass different,not allow
turn on UPS. Check bypass
input
Check UPS OP mode, Keep
OP mode be the same
Rate power different,not
allow turn on UPS. Keep
rate power be the same
HE not allow in parallel
system,change OP mode