Figure 1a: M201E-240 ( -KO ) Surface Mount
Output Module with 240V Relay Contacts
Figure 1b: M201E-240-DIN Din Rail Mounted
Output Module with 240V Relay Contacts.
TO MOUNT, LOCATE LUG OVER TOP
OF RAIL AND ROTATE THE MODULE
DOWN TO CLIP INTO PLACE.
TO REMOVE, PUSH UPWARDS, AND
ROTATE TOP OF MODULE AWAY
FROM RAIL.
Figure 2: Module Wiring
NOTE: Wiring is the same for M201E-240 ( -KO ) and M201E-240-DIN
Relay 1, N/O
7
Relay 2, N/C
8
Ground
9
Ground
10
Relay 2, N/C
11
Relay 1, N/O
12
8 9
6 7
5
4
3
2
1
0
TENS
ROTARY DECADE ADDRESS SWITCHES
Notes:
1. If short circuit isolation is not required, then the loop output should
be wired to terminal 5 rather than terminal 2. Terminal 5 is internally
connected directly to terminal 4.
2. In order to meet the requirements of European Safety Standards,
ensure that all cables carrying voltages in excess of 48V are suitably
fused.
D200-93-01
M201E-240, M201E-240-KO
INSTALLATION INSTRUCTIONS FOR MAINS
SWITCHING OUTPUT MODULES
LOOP CABLE SCREEN TERMINAL
Loop -, Out
1
Loop +, Out - See Note 1
2
Loop -, In
3
Loop +, In
4
Loop +, Out - See Note 1
5
T6 - Not Connected
6
8 9
6 7
10
11
5
4
12
3
13
2
14
1
15
0
UNITS
DoP Ref: 0786-CPD-20341
EN54-17: 2005 , EN54-18: 2005
System Sensor Europe
Life Safety Distribution GmbH
Javastrasse 2, 8604 Hegnau,
0786 07
Switzerland
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
M201E-240-DIN
AND
This manual is intended as a quick reference installation guide. Please refer
to the control panel manufacturers installation manual for detailed system
information
GENERAL INFORMATION
The M200+ series of modules are a family of microprocessor controlled
interface devices permitting the monitoring and/or control of auxiliary
devices. The M201E-240, M201E-240-KO and M201E-240-DIN are output
modules, providing 250VAC 5A rated voltage free contacts, both normally
open and normally closed.
SPECIFICATIONS
Operating Voltage Range:
15 to 30VDC (Min 19.5VDC to ensure LED
operation - M201E-240-KO 17.5VDC)
Maximum Standby Current (µA): 275µA - No Communication
445µA - Communication LED blink enabled - 5 secs
375µA - Read 16 sec. LED blink 8 sec
Fault Current:
8.8mA (Yellow LED illuminated)
Coil Activation/Deactivation Current: 76mA Maximum for 12mS
Relay Contact Rating:
5A, at 30VDC, 5A at 250VAC
Maximum rated continuous current with the
Maximum rated isolator current (under short circuit) (I
Maximum leakage current (I
max) with the isolator open (isolated state): 15mA
L
Maximum series impedance with the isolator closed (Z
Operating Temperature:
-20°C to 60°C
Humidity:
5% to 95% Relative Humidity
Dimensions M201E-240 and M201E-240-KO: 134mm(H) x 139mm(W) x 40mm(D)
Dimensions M201E-240-DIN:
127mm(H) x 76mm(W) x 48mm(D) (Including terminals)
Weight M201E-240 and M201E-240-KO: 195g
Weight M201E-240-DIN:
140g
Maximum Wire Gauge
1.5mm² - M201E-240 (-KO), 2.5mm² - (-DIN)
INSTALLATION
Note: These modules must only be connected to control panels using
compatible proprietary analogue addressable communication
protocols for monitoring and control.
Disconnect loop power before installing modules or sensors.
High voltages may be present on terminals 7 to 12.
M201E-240 and M201E-240 -KO
1. The M201E-240 ( -KO ) includes a custom low profile surface-mounting
box with several options for fixing centres. To access all fixing points,
and the rear cable entry knock out, the circuit board must be removed.
It is held in place by two screws through the circuit board. Ensure that
these screws are replaced when refitting the circuit board.
2. If rear cable entry is not required, the box has several cover drill points
permitting the entry of cables using suitable glands.
3. Wiring to the M201E-240 ( -KO ) is made via two 6 way terminal strips
on the module circuit board, capable of supporting conductors up to
1.5mm². See figure 2 for connections.
4. An earthing terminal is provided in the surface mount box for connection
of the loop cable screen, if used, to ensure continuity. See figure 1a.
M201E-240-DIN
1. M201E-240-DIN mounts onto standard 35mm x 7.5mm "Top Hat" DIN
rail. It must be mounted in a suitable cabinet meeting the applicable
safety standards.
2. Wiring to the M201E-240-DIN is via plug in type terminals capable of
supporting conductors up to 2.5mm². See figure 2 for connections.
Ensure that the correct terminals are used for the loop and
switched voltage as damage may result from incorrect usage.
For both modules, the address is selected by means of rotary decade
address switches (see figure 2), accessed at the front of the module. A
screwdriver should be used to rotate the wheels to select the desired
address. (Note: The number of addresses available will be dependent on
panel capability, check the panel documentation for information on this.)
Short Circuit Isolators
All M200+ series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired out of
the loop to facilitate the use of the modules on high current loaded loops, for
example if sounders are used. To achieve this, the loop out positive should
be wired to terminal 5 rather than terminal 2.
E N G L I S H
I 56- 1768- 015
isolator
closed (I
max): 1A
c
max): 1A
s
max): 170 m ohm at 15Vdc
c
CAUTION
WARNING
I56-1768-015

Werbung

loading

Inhaltszusammenfassung für System Sensor M201E-240

  • Seite 1 2. If rear cable entry is not required, the box has several cover drill points permitting the entry of cables using suitable glands. 3. Wiring to the M201E-240 ( -KO ) is made via two 6 way terminal strips on the module circuit board, capable of supporting conductors up to Figure 2: Module Wiring 1.5mm². See figure 2 for connections.
  • Seite 2 Umidità: Umidità relativa compresa tra il 5% e il 95% (in assenza di condensa) Dimensioni del modello M201E-240(-KO): 134 mm (H) x 139 mm (L) x 40 mm (P) Dimensioni del modello -DIN:127 mm (H) x 76 mm (L) x 48 mm (P) (compresi i morsetti) Peso del modello M201E-240(-KO): 195 gr.
  • Seite 3 PARA DESMONTARLO, M201E-240 y M201E-240-KO EMPUJE HACIA ARRIBA Y GIRE 1. El M201E-240 ( -KO ) incluye una caja a medida de bajo perfil para montaje LA PARTE SUPERIOR DEL en superficie, con varias opciones para los centros de sujeción. Para MÓDULO PARA SEPARARLO...
  • Seite 4 Bohrlöcher der Abdeckung in Verbindung mit geeigneten Kabelmanschetten genutzt werden. 3. Die Verdrahtung des M201E-240 ( -KO ) erfolgt über die 6-poligen Anschlussleisten auf der Platine mit einem zulässigen Kabelquerschnitt von max. 1,5mm² ( Anschluss siehe Abbildung 2).

Diese Anleitung auch für:

M201e-240-koM201e-240-dinM201ea-240