(7) Fault finding
WARNING: Maintenance work shall have to be carried out with the unit switched off, i.e. with mains
plug removed.
Display C
PROBLEM
0101
None
rHxx
None
Decy
None
Full
Alarm 1
Lo t
Alarm 2
Lo T
Alarm 3
LOPt
Alarm 4
Hi T
Alarm 5
Hi T
Alarm 6
Prob
Alarm 7
Pro1
Alarm 8
Pro2
Alarm 8
Pro3
Alarm 8
LOPS
Alarm 9
HIPS
Alarm 10
Performer: B - user , AST - authorised service technician
All manuals and user guides at all-guides.com
CAUSE
After plugging the mains
plug, the version of the
software is displayed
Display of relative air
humidity
Device in defrosting mode
Condensate tank is full
Defrosting has failed
Ambient temperature below
1 deg. C
Temperature difference too
low
(dew-point not made)
Ambient temperature over
36 deg. C
Humidity < 75 per cent rH
Ambient temperature over
30 deg. C
Humidity > 78 per cent rH
Moisture probe - ambient
temperature outside nominal
value
Temp. Vaporiser sensor T1
Temp. Vaporiser sensor T2
Temp. Sensor Room temp.
T3
Low-pressure alarm
High-pressure alarm
22
Version
Solution
The display goes off after
approx. 4 s.
Device starts automatically after
max. 8 min.
B
Empty tank and place it
B
Pull mains plug and after 10 s
switch on again
B
Place device in room with > 10
deg. C for 30 s.
Alarm is reset automatically.
B
Device starts after 210 s
automatically; after three
failures, press button 3+4 (press
for 10 s) to reset.
B
Automatic start, if temperature <
35 deg. C
B
Automatic start, if temperature <
30 deg. C
B / AST Device continues to run; if fault
occurs again, contact service
AST
Contact HEYLO service
department
AST
Contact HEYLO service
department
AST
Contact HEYLO service
department
B/AST
Check ambient temperature;
reset unit with 3+4 button.
B/AST
Check ambient temperature;
reset unit with 3+4 button.