Herunterladen Diese Seite drucken

STIEBEL ELTRON HSBC 200 Bedienung Und Installation Seite 48

Integralspeicher

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
INSTALLATIoN
Commissioning
12.2.2 Fitting the temperature sensor (accessory) for area
cooling
Area cooling requires the fitting of a temperature sensor, available
as an accessory.
f Remove the front casing (see chapter "Preparations / Trans-
f
port and handling / Removing / fitting the front casing").
f Insert the temperature sensor into the sensor well "Sensor
f
heat pump cooling, optional".
f Connect the temperature sensor to AA01-X1.11.
f
12.3 Remote control
12.3.1 FE 7 remote control
With the FE 7 remote control you can adjust the set room tempera-
ture for heating circuit 1 or heating circuit 2 by ± 5 °C in automatic
mode only. You can also select the operating mode.
f Connect the remote control to AA01-X1.13.
f
48
| HSBC
12.3.2 FET remote control
6
5
With the FET remote control you can select the operating mode
and change the set room temperature for heating circuit 1 or
heating circuit 2 by ± 5 °C.
f Connect the remote control to AA01-X1.2.
f
13. Commissioning
Our customer support can assist with commissioning, which is a
chargeable service.
If the appliance is intended for commercial use, observe the rules
of the relevant Health & Safety at Work Act during commissioning.
For further details, check with your local authorising body (in
Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump
manager
Material losses
!
Observe the maximum system temperature in underfloor
heating systems.
f Check that the heating system is filled to the correct pressure
f
and the quick-action air vent valve is closed.
f Check whether the outside temperature sensor is correctly
f
placed and connected.
f Check whether the power supply is connected correctly.
f
f Check whether the signal cable to the heat pump (bus cable)
f
is correctly connected.
4
3
2
1
+
L
H