Herunterladen Diese Seite drucken

Victron energy Quattro 24/5000/120 Anleitung Seite 24

Vorschau ausblenden Andere Handbücher für Quattro 24/5000/120:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 75
Bulk LED off
Absorption LED
off
flashing
off
0
3
flashin
1
4
g
on
2
5
Bulk LED
Code
Absorption LED
Float LED
Device is switched off because
1
one of the other phases in the
3
expected devices were found in
No other device whatsoever
4
5
System time synchronisation
10
14
Device cannot transmit data.
One of the devices has assumed
17
'master' status because the
18
Overvoltage has occurred.
This device cannot function as
22
Switch-over system protection
24
Firmware incompatibility. The
firmware of one the connected
25
devices is not sufficiently up to
date to operate in conjunction
26
22
Bulk LED flashes
On
6
off
flashin
7
g
8
on
Meaning:
system has switched off.
Not all, or more than, the
the system.
detected.
Overvoltage on AC-out.
problem occurred.
original master failed.
'slave'.
initiated.
with this device.
Internal error.
Absorption LED
off
flashing
on
9
12
15
10
13
16
11
14
17
Cause/solution:
Check the failing phase.
The system is not properly configured. Reconfigure the system.
Communication cable error. Check the cables and switch all
equipment off, and then on again.
Check the communication cables.
Check the AC cables.
Should not occur in correctly installed equipment. Check the
communication cables.
Check the communication cables (there may be a short circuit).
Check the failing unit. Check the communication cables.
Check AC cables.
This device is an obsolete and unsuitable model. It should be
replaced.
Should not occur in correctly installed equipment. Switch all
equipment off, and then on again. If the problem recurs, check
the installation.
Possible solution: increase lower limit of AC input voltage
to 210VAC (factory setting is 180VAC)
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error
message reoccurs.
4) Update the firmware in the last device that was switched on.
Should not occur. Switch all equipment off, and then on again.
Contact Victron Energy if the problem persists.
Bulk LED on
Absorption LED
off
flashing
on
off
18
21
24
flashin
19
22
25
g
on
20
23
26

Werbung

loading

Diese Anleitung auch für:

Quattro 48/5000/70