Herunterladen Diese Seite drucken

Eaton CROUSE-HINDS CEAG GHG 512 Betriebsanleitung Seite 18

Explosionsgeschützte steckvorrichtungen 32 a, 4-polig, 5-polig
Vorschau ausblenden Andere Handbücher für CROUSE-HINDS CEAG GHG 512:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code for voltage and No. of poles
acc. to UL
Voltage
Colour face
2-pole + PE
(PE)
125V 60Hz
yellow
250V 60Hz
blue
480V 60Hz
red
3-pole + PE
600V 60Hz
black
480V 60Hz
red
250V 40Hz
blue
125/250V 60Hz
orange 12 h
3-pole + N + PE
600V 60Hz
black
277V 60Hz
red
120/208V 60Hz
blue
Dimensions in mm
X = fixing dimensions
Wall socket, 4-pole
Wall socket, 5-pole
2 2 2 2 2
Cooper Crouse-Hinds GmbH
Annex to operating instructions
Plug and socket system 30A, GHG 512
1 1 1 1 1
T T T T T echnical data
echnical data
echnical data
echnical data
echnical data
1.1
1.1
1.1
1.1
1.1
Plug and socket GHG 512
Plug and socket GHG 512
Plug and socket GHG 512
Plug and socket GHG 512
Plug and socket GHG 512
Explosion catagory:
for USL
for CNL
Certifications and Compliances:
for USL
for CNL
Rated voltage:
Clock
Rated current:
Back-up fuse:
without thermal protection
4 h
with thermal protection
6 h
Switching capacity:
7 h
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
5 h
Protection category acc. to IEC 60529
7 h
with closed and secured hinged cover as well
9 h
as combinations properly plugged together
Insulation class acc. to IEC61140:
Cable entry:
Wall socket
5 h
plug / Coupler
7 h
Supply terminal:
9 h
Wall socket
Coupler
Flange socket
Plug
Test torques:
Cover screws
Terminals wall-; flange socket
Terminals plug
Self-cutting screws size 4
Self-cutting screws size 5
Weight:
Wall socket
Plug
Coupler
Flange socket
Wall socket
Plug
Coupler
Flange socket
Auxiliary contact:
Rated voltage:
Rated current:
AEx de II C T6
Ex de II C T6
Class I, Zone 1
Class I, Division 2 -
Class I, Zone 1
Class I, Division 2 -
Class II, Division 1 -
up to 600 V, 60 Hz
max. 30 A
max. 30 A
max. 50A gL
690V / 30A
-20° C to + 40° C (catalogue version)
-55° C to + 80° C
IP 66 (catalogue version)
(catalogue version)
2 x M32, (1 x hub M32 / 1"NPT, 1 x blanking plug)
Ø 12 - 28 mm
Cross section
2 x AWG 16 - 12
2 x AWG 16 - 12
2 x AWG 16 - 12
1 x AWG 17 - 14
22.0 Lb-in.
22.0 Lb-in.
13.2 Lb-in.
14.2 Lb-in.
26.0 Lb-in.
4-pole
GHG 512 44
approx.2.25 kg (incl. hub M32 /1" NPT)
4-pole
GHG 512 74
approx.0.55 kg
4-pole
GHG 512 34
approx.1.50 kg
4-pole
GHG 512 84
approx.1.00 kg
5-pole
GHG 512 45
approx.2.30 kg (incl. hub M32 /1" NPT)
5-pole
GHG 512 75
approx.0.60 kg
5-pole
GHG 512 35
approx.1.60 kg
5-pole
GHG 512 85
approx.1.05 kg
250 VAC
AC / 5 A
Groups A, B, C and D
Groups A, B, C and D
Groups E, F and G
I - is complied with by the devices
Stripped wire length
12 mm
12 mm
12 mm
10 mm
DC / 0.03 A

Werbung

loading

Diese Anleitung auch für:

Crouse-hinds-serieCrouse-hinds ghg 512