INSTRUCTION
EN
ED-RU-O
i
Read this instruction before installation
and wiring of the product
Room unit for basic controller configuration or
enduser control
ED-RU-O is an external room unit primarily intended for control of
an air handling unit, heating unit or room controller.
Perform basic controller configuration, or let the person in the room
control the room's HVAC behaviour, via a connected ED-RU... room
unit. Choose from a large selection of room units that fit your specific
needs..
Technical data
Supply voltage
24 V AC/DC
Power consumption
25 mA
Protection class
IP20
Ambient humidity
Max. 90 % RH
Ambient temperature
0...50°C
Storage temperature
-20...+70°C
Mounting
On wall or device box
Communication
EXOline
Wiring
Based on the used controller there are two different wiring options:
1. The room unit can be connected to the same supply voltage as the
controller (G and G0). Communication then takes place via EXOline
and is connected to the serial ports (RS485), A and B.
G
G0
42
A
A
B
43
B
Figure 1 Wiring
2. They can also be connected via an EDSP-K3 cable to the display port.
ED-RU-...
10 G
11
G0
EDSP-K3
42
A
43
B
Figure 2 Wiring with an EDSP-K3 cable
Terminal N and
EDSP-K3 wire color
designator
10 G
Black
24 V AC supply voltage input
11 G0
White
24 V AC voltage reference
42 A
Yellow
Output signal to controller
43 B
Brown
Input signal to controller
ED-RU-O
The On/Off button using Application tool
Regio Eedo/Ardo provides several options to manage controller state
changes, that is changes between a comfort and an energy-saving
operational mode. For example, state changes can be managed by:
– Pressing the occupancy button on the room unit to increase the
airflow.
– Detecting presence in the room via a CO
10
detector.
24 V AC
11
The On/Off button using E-tool
The function of the On/Off button can be configured using E tool.
Setting
No function
On/Off
On/off/extended
running
When pressing the On/Off button for 10 s, the air handling unit will
stop. At the next scheduled start-up it will then start and run in mode
AUTO.
A press of the button will start the unit, making it run at normal speed
for the duration set under "extended running" (factory setting 60 min.).
Thereafter, the unit will enter into auto mode.
The setpoint knob
Enables adjusting the setpoint up or down. The maximum permiss-
able adjustment of the setpoint is configurable using E tool
setting ± 3°C).
Depending on the control mode of the Corrigo, the setpoint knob will
Description
adjust the actual setpoint. In control mode constant supply air control,
the supply air setpoint will be adjusted. In room cascade, the room
setpoint will be adjusted. If the control mode is extract air cascade,
the extract air setpoint will be adjusted.
This product carries the CE-mark.
More information is available at www.regincontrols.com.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, info@regincontrols.com
sensor or a motion
2
Description
Pressing the button has no effect.
The button can be used to turn the
unit off or place it in auto mode
The button can be used to turn the
unit off or to force it to run in normal
speed for a settable duration, after
which it will enter auto mode.
(factory
©
1

Werbung

loading

Inhaltszusammenfassung für Regin ED-RU-O

  • Seite 1 EDSP-K3 The setpoint knob ED-RU-O is an external room unit primarily intended for control of Enables adjusting the setpoint up or down. The maximum permiss- an air handling unit, heating unit or room controller. able adjustment of the setpoint is configurable using E tool (factory ©...
  • Seite 2 Om det är frånluftskaskad justeras frånluftsbörvärdet. Rumsenheter för grundläggande regulator- konfiguration eller slutanvändarkontroll Figur 2 Inkoppling med en EDSP-K3-kabel ED-RU-O är en extern rumsenhet, främst avsedd för styrning av Denna produkt är CE-märkt. Mer information finns på www.regincontrols.com. luftaggregat, värmeenhet eller rumsregulator.
  • Seite 3 Die Taste kann benutzt werden, um Bild 2 Verdrahtung mit einem EDSP-K3 Kabel die Anlage auszuschalten, oder sie ED-RU-O ist ein externes Raumgerät, das vor allem zur Regelung für eine bestimmte Dauer auf Stufe einer Lüftungsanlage, einer Heizungsanlage oder als Raumregler...