Included:
(5) 1 × 4 Terminal Blocks
(2) 3.2 cm Stand offs
(1) Long Power Supply Jumper
(Shipped on Board:
(2) Shunts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
compatible system control panel. Contact Morley IAS for a list of
compatible detectors. The MI-CZ6 Module shall be mounted in a
suitably grounded Metallic Cabinet for EMC compliance.
WIRING
NOTE: All wiring must conform to applicable local codes, ordi-
nances, and regulations.
1.
Install module wiring in accordance with the job drawings
and appropriate wiring diagrams.
Figure 1. Interface two-wire conventional detectors:
1.
To use a common power supply between multiple MI-CZ6
modules, connect a long power supply jumper from T5 or T6
to T5 or T6 on the adjacent MI-CZ6 module.
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
3.9K EOL
RESISTOR
(INCLUDED)
+
CLASS B IDC (TYPICAL)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
COMMUNICATION LINE 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
M450-04-00
(4) Screws
(2) Nuts
(3) Shunts
(6) 3.9k Ohm End of Line Resistors
C0907-00
+
(+)
(–)
POWER-LIMITED
AND SUPERVISED
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2.
All wiring to the MI-CZ6 is done via terminal blocks. In order
to properly make electrical connections strip approximately 5
mm of insulation from the end of wire, sliding the bare end of
the wire under the clamping plate screw.
3.
Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module
(between 01 and 94).
The remaining modules are automatically assigned to the next
five higher addresses. For example, if the base address switch is
set to 28, the next five modules will be addressed to 29, 30, 31,
32 and 33.
DO NOT set the lowest address above 94, as the other modules
will be assigned to nonexistent addresses.
4.
A shunt is provided to disable a maximum of two unused
modules. Modules are disabled from the highest address and
work downward. If two modules are disabled, the lowest four ad-
dresses will be functional, while the highest two will be disabled.
For example, if the shunt for Address Disable is placed on "two"
and the base switch is set to 28, the modules will be assigned to
28, 29, 30 and 31 while disabling the highest two positions.
NOTE: Place unused shunts on single pin to store on board for
future use.
WIRING NOTES
• All external power supplies must be power limited with battery
back-up.
BASE ADDRESS
6 7 8 9
5
4
3
2
1
0
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
2
6 7 8 9
5
4
3
2
1
0
STATUS
INDICATORS
I56-2954-000
C0199-00