TECHNICAL DATA (continued)
Sludge Level Probe (NivOil SP)
Exclusively for connection to the sensor supply unit (NivOil CU)!
Material sensor
Cable
Cable colour
Dimensions
Protection
Measuring principle
Ambient temperature
EU Type Examination Certificate BVS 09 ATEX E 021 X
Ex-maximum values
Maximum input voltage Ui
Maximum input current Ii
Maximum input power Pi
Maximum internal capacity Ci
Maximum internal inductance Li
Ex marking
Interconnection
Note!
Use only in stagnant or slow-flowing media.
Strong mechanical impacts on the probe housing must be avoided during installation, maintenance work and operation.
Clean only with a damp cloth, avoid electrostatic discharges.
Special conditions for safe use
The connection line of the sludge level probe (NivOil SP) must be routed through the separation between areas with category 1G requirements
and less hazardous areas in such a way that protection class IP67 in accordance with EN 60529 is ensured.
The sludge level probe (NivOil SP) and connection cable may only be used in areas where electrostatic discharges cannot occur.
The technical information for using the sludge level probe (NivOil SP)
- in connection with aggressive/corrosive media
- with regard to protection against impact
- with regard to the flow velocity of the media
- Cleaning
are to be observed.
EN
M-531.01-EN-AK du 30-06-2023 - Manufacturer : BAMO IER - Pirnaer Straße 24, D-68309 Mannheim - Germany (Translated document)
PVC
Standard with 10m oil / petrol resistant cable 2x1mm²
Other cable lengths on request
Maximum permissible cable length: 300m
[C ≤ 200 nF/km and L ≤ 1 mH/km]
blue
ca. 145x90x25mm
IP68
Ultrasound
-20°C...+60°C
17.9V DC
157mA
695mW
0.14nF/m
(no mixed parameters)
70μH/m
(no mixed parameters)
㐀 II 1G Ex ia IIB T4 Ga
(intrinsically safe electrical equipment)