Herunterladen Diese Seite drucken

SOMFY animeo 1860209 Gebrauchsanweisung Seite 8

Ib+ 2 ac motor controller wm/pcb 100-230 v ac

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
EN
A
PICTURES
[1] animeo 2 AC Motor Controller WM 100-230 V AC,
wall mounted version
[2] animeo 2 AC Motor Controller PCB 100-230 V AC,
PCB version (with DIN rail clip, Ref. 9008049)
B
MOUNTING
[1] Choose the optimal location: flat and large surface
or electric cabinet. Close door!
[2] Use cable tie!
[3] Mount the 2 AC Motor Controller WM
[4] Mount the DIN rail version
1.
Vertical (wall mounted or PCB version)
2.
Horizontal (wall mounted version)
C
WIRING
[1] Complete the wiring and connect power supply
[2] Insulated screwdriver
[3] Wiring diagram
[4] Check the correct running directions of the
end product
UP: the end product goes up ( C + s)
STOP: the end product stops ( C + t+ s)
DOWN: the end product goes down ( C + t)
n To close window press UP,
to open window press DOWN.
[5] Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button
CABLE
Connection to ...
Motors
Switches
IB+ bus
100-230 V AC
Cable
Min.:
4 x 0.75 mm
/18 AWG
2
Max.:
4 x 2.5 mm
/14 AWG
2
Min.:
3 x 0.6 mm/22 AWG
Max.:
3 x 2.5 mm
/14 AWG
2
Min.:
4 x 0.6 mm/22 AWG
Max.:
4 x 1.5 mm
/16 AWG
2
Min.:
3 x 1.5 mm
/16 AWG
2
Max.:
3 x 2.5 mm
/13 AWG
2
D
CONFIGURATION
[1]
Reset / Prog button
With this button, you can access the basic
configuration of the Motor Controller.
1.
Wall mounted version
2.
PCB version
[2]
Selection of switch ergonomic
Local push button ergonomics and the type of end
products to be preselected:
• Screen mode
• Venetian blind, European mode (default mode)
• Venetian blind, US mode
1.
To toggle between modes, press the Reset / Prog
button 2 s. Repeat until the LED, according to
the desired configuration, lights up. Store by
pressing 2 s.
[3]
Factory RESET
[4]
Learn running time/length
1.
Drive screen to upper end limit
2.
Press Stop until screen drives down on its own
3.
Press Stop when lower end limit is reached
[5]
Symbols: actions
1.
Up
2.
Stop
3.
Down
[6]
Symbols: end product status
1.
Up
2.
Upper end position
3.
Down
4.
Lower end position
m When electronic motors are to be controlled through this
Motor Controller device it is mandatory to configure the
start-up delay time for electronic motors in the Motor
Controller settings. To configure the start-up delay time WT
Setting Tool Ref. 1811242 can be used.
Twisted pair
-
Recommended
Recommended
-
animeo IB+ 2 AC MOTOR CONTROLLER . REF. 5102774 C -
Max. length
150 m
100 m
1000 m
8/16

Werbung

loading

Diese Anleitung auch für:

Animeo 1860210