aerex Reco-Boxx 140 Flat Installations-, Gebrauchs- Und Wartungsanleitung Seite 12

Horizontale installation

Werbung

ENGLISH
The appliance must not be used to activate water heaters, room heaters, etc.
The appliance must absolutely not
the combustion of stoves or other combustion devices.
It must be connected to a ducting system for its exclusive usage.
WARNING: Damage can be caused to the device if the following instructions are not applied!
Do not use the product at ambient temperatures above 50°C or lower than 5°C or in areas of humidity levels
above 90% or in a wet environment.
Do not leave the appliance exposed to atmospheric agents (rain, sun, snow, etc.).
Do not immerse the appliance or parts of it in water or any other liquids.
When cleaning or carrying out ordinary maintenance, check the integrity of the appliance.
The flow of air or fumes that is conveyed by the appliance must be clean and free of greasy elements, soot,
chemical/corrosive agents and inflammable or explosive mixtures.
The devices connected to the mains supply must allow complete disconnection in the conditions of overvoltage
category III (permanent connection).
Do
not obstruct in any way the outlet ports, air exhaust and the pipes.
If there is a combustible-fed device (water heater, gas boiler, etc. of the sealed chamber type) in the room where
the product is to be installed check that the re-circulation of air is sufficient to ensure a good combustion for the
correct functioning of these devices.
The unit is not suitable for outdoor installation.
Note: Possible applications for this product may be inferred by the illustrations in this booklet!
Functioning
This appliance has been designed to operate continuously and to create a stable, comfortable, healthy environment
avoiding the use of excessive energy. It provides a centralized and controlled ventilation of the residential premises and
recovers the thermal energy of the extract air stream (heat in winter, cold in summer). It extracts stale, contaminated
air from the technical rooms (kitchens, utility rooms and bathrooms), and gives the thermal energy recovered from
the extract air way to the clean, incoming air to create a flow of fresh, filtered air throughout the dwelling (living rooms
and bedrooms).
Note: This unit is designed to run continuously. If it is switched off, indoor pollutant and moisture levels may
increase.
Operative choices:
2 SPEED OPERATION - DiagramNo.1
This appliance provides a continuous running operation at the minimum speed; there is a facility to boost the extraction
rate when desired (e.g. when cooking or bathing, or when pollutant levels rise).
The high speed can be activated by means of a remote control, e.g. dedicated switch or humidity, PIR or air quality
sensor. The boost can be also activated by means of a volt-free contact. Both speeds can be adjusted during
commissioning by the appropriate trimmers.
3 SPEED OPERATION (with RB-ZF 4 external regulator) - DiagramNo.2
This appliance provides a continuous running operation at the minimum speed, with the option to select medium or
maximum speed by switching UP or DOWN on RB-ZF 4 regulator. On the regulator front panel leds I (minimum), II
(medium), and III (maximum) show the actual operative speed.
If DOWN switch is selected during minimum speed operation, the device will stop the motors (STAND-BY) and warn
the operator by flashing of led I. To re-activate the device UP switch must be selected.
FILTER CLEANING/REPLACEMENT WARNING: periodically (every 3 months) the flashing of the 3 leds on RB-ZF
4 regulator warns the operator to clean/replace filters; after the maintenance has been carried out, UP and DOWN
switches must be pushed together for more than 5 seconds.
The 3 speeds can be regulated during installation with the trimmers located on the circuit board (see Diagram
No.2)
S. 12
discharge air into hot air ducts used for the evacuation of fumes coming from
AEREX RECO-BOXX 140 FLAT