Mounting and Connection Instructions IB2 Bus Expander
4.
Mounting
4.1
Guidelines
Mounting on the metal housing base of the control panel or in a separate metal housing.
The circuit board size corresponds with the existing I-BUS modules.
Please refer to Chapter "Grounding and Shielding" in the Instructions for the Installer of the MB-
Secure control panel.
In a housing, which is designed for subsequently installation of a lock, a VdS certified
lock insert (e.g. 028051) has to be installed instead of a plastic cover for systems
according to VdS and EN.
For systems, in which the panel is not conform to the EN guidelines, the EN-markings
have to be removed from the panel.
4.2
Mounting in the control panel housing
PE
4.3
Mounting in a separate metal housing
When installing the module in a separate housing, use a suitable housing from our catalog.
As per EN only MB-Secure housings are permitted
Permitted cable lenth between panel and module up to 2000 m (see 5.3.2).
Install the PCB
Mount the circuit board with the supplied fixing material on the housing base.
Screw the corner of the circuit board marked with PE (see fig. above) using a metal screw to the
metal bolt on the housing base.
Required tamper monitoring
For the tamper monitoring the cover contact of the housing and a tear-off protection must be used. The
complete tear-off protection incl. spacers in various lengths is available as accessory, Item no. 055140
(PU = 5 piece). The Mounting Instruction P02916-47-002-xx is included.
Use 2 of the 4 analogue inputs (see chapter 6.3) to connect the cover contact and the tear-off
protection. Program the inputs as tamper detector group.
Mount the circuit board with the supplied fixing material on
the housing base.
Screw the corner of the circuit board marked with PE using a
metal screw to the metal bolt on the housing base.
(ZG20, ZG2, ZG3.1 or ZG4).
15