Herunterladen Diese Seite drucken

Siemens 6AG1193-6AA00-0AA0 Kompaktmontageanleitung Seite 7

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation
The SIPLUS Mounting Kit ET 200SP is intended for mounting on the standard mounting rail included in the scope of delivery.
1. If necessary, shorten the standard mounting rail ⑧ and the C-section rail ① to the required length.
2. Mount the standard mounting rail ⑧.
3. If necessary, shorten the damping material ② according to the length of the C-section rail minus 32 mm.
4. Mount the end brackets ⑦ and ⑨ of the SIPLUS Mounting Kit ET 200SP in such a way that the end brackets are in contact
with the SIPLUS ET 200SP system without a gap.
5. Glue the damping material ② centrally onto the C-section rail ①.
Make sure that the damping material does not rest on the end brackets.
It is essential to degrease and clean the C mounting rail with grease-dissolving cleaning agents.
6. Tighten 2 × 4 screws ⑥ with a torque of 2.1 Nm.
7. Mount the C-section rail ① with the glued-on damping material ②.
8. Push the clip ⑤ of both end brackets into the C-section rail ① up to the stop.
9. Tighten the two screws ③ with a torque of 2.1 Nm.
a
Pre-cut part of the C-section rail = total length - 52 mm
b
Pre-cut part of the damping material = C-section rail - 32 mm
c
Total length = length of the lined-up modules + 2x width of an end bracket
Mounting Kit ET 200SP
A5E47207185B/003, 07/2021
7

Werbung

loading

Diese Anleitung auch für:

Siplus mounting kit et 200sp