Define input signal on the analog input
AIA: 0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3: Displacement of superheat reference. 0-20
mA 4: Displacement of superheat reference.
4-20 mA
Set supply voltage frequency
Select display for "normal picture"
(Display the item indicated in parenthesis
by briefly pressing the bottom button)
1: Superheat (Temperature)
2: Valve's opening degree (Superheat)
3: Air temperature (Temperature reference)
Manual control of outputs:
OFF: no manual control
1: Relay for solenoid valve: select
ON 2: AKV/A output: select ON
3: Alarm relay activated (cut out)
Working range for pressure transmitter – min.
value
Working range for pressure transmitter – max.
value
(Setting for the function o09, only AKV and
TQ) Set the temperature value or opening
degree where the output signal must be
minimum (0 or
4 mA)
(Setting for the function o09, only AKV and
TQ) Set the temperature value or opening
degree where the output signal must be
maximum (20
mA)
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13.
7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114.
12=R142b. 13=User defined. 14=R32. 15=R227.
16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C.
21=R407A.
22=R407B. 23=R410A. 24=R170. 25=R290.
26=R600.
27=R600a. 28=R744. 29=R1270. 30=R417A.
31=R422A.
32=R413A. 33=R422D. 34=R427A. 35=R438A
Service
TQ valve's actuator temperature
Reference of the valve's actuator temperature
Analog input AIA (18-19)
Analog output AO (2-5)
Read status of input DI
Thermostat cut-in time
Temperature at S2 sensor
Superheat
Superheat reference
Read AKV valve's opening degree
Read evaporating pressure
Read evaporating temperature
*) This setting will only be possible if a data communication module has been installed in the controller.
Temperature at S3 sensor
Temperature reference
Factory setting
Read signal at pressure transmitter input
If you need to return to the factory-set values, it can be done in this way:
-
Cut out the supply voltage to the controller
-
Keep both buttons depressed at the same time as you reconnect the supply voltage
© Danfoss | DCS (ADAP-KOOL®) | 2015-03
User Guide | Superheat controller, EKC 315A
o10
0
4
0
o12
50 Hz
60 Hz 0
o17
1
3
1
o18
off
3
Off
o20
-1 bar
60 bar -1.0
o21
-1 bar
60 bar 12
o27
-70°C
160°C -35
o28
-70°C
160°C 15
o30
0
35
0
u04
°C
u05
°C
u06
mA
u08
mA
u10
on/off
u18
min.
u20
°C
u21
K
u22
K
u24
%
u25
bar
u26
°C
u27
°C
u28
°C
u29
mA
a
The controller can give the following messages:
E1
Fault in controller
Valve's actuator temperature outside its range
E11
E15
Cut-out S2 sensor
E16
Shortcircuited S2 sensor
E17
Cut-out S3 sensor
Error message
E18
Shortcircuited S3 sensor
The input signal on terminals 18-19 is
E19
outside the range.
The input signal on terminals 14-15 is
E20
outside the range (P0 signal)
A1
High-temperature alarm
A2
Low-temperature alarm
Alarm message
A11
No refrigerant has been selected
DKRCI.PS.RP0.D2.02 | 520H76