Survey of functions
Function
Normal display
Normally the superheat is shown (but the valve's opening degree or air temperature may also be selected.
See o17).
Reference
Se point
Regulation is performed based on the set value provided that there is no external contribution (o10).
(Push both buttons simultaneously to set the setpoint).
Differential
When the temperature is higher than the reference plus the set differential, the sole- noid valve's relay
will be activated. It will become deactivated when the temperature drops below the set reference.
Unit
Here you select whether the controller is to indicate the temperature values in °C or in °F. If indication in
°F is selected, other temperature settings will also change over to Fahrenheit, either as absolute values or
as delta values
The combination of temperature unit and pressure unit is depicted to the right.
External contribution to the reference
This setting determines how large a contribution is to be added to the set setpoint when the input signal is
max. (20 mA). See o10.
Correction of signal from S2
(Compensation possibility through long sensor cable).
Correction of signal from S3
(Compensation possibility through long sensor cable).
Start/stop of refrigeration
With this setting refrigeration can be started and stopped. Start/stop of refrigeration can also be
accomplished with the external switch function. See also appendix 1.
Define thermostat function
0: No thermostat function. Only the superheat is regulated 1: Thermostat
function as well as regulation of superheat.
Alarm
The controller can give alarm in different situations. When there is an alarm all the light-emitting diodes
(LED) will flash on the controller front panel, and the alarm relay will cut in.
Alarm for upper deviation
The alarm for too high S3 temperature is set here. The value is set in Kelvin. The alarm becomes active
when the S3 temperature exceeds the actual reference plus A01. (The actual reference can be seen in
u28).
Alarm for lower deviation
The alarm for too low S3 temperature is set here. The value is set in Kelvin. The alarm becomes active
when the S3 temperature drops below the actual reference minus A02.
Alarm delay
If one of the two limit values is exceeded, a timer function will commence. The alarm will not become
active until the set time delay has been passed. The time delay is set in minutes.
User Guide | Superheat controller, EKC 315A
Ref.
© Danfoss | DCS (ADAP-KOOL®) | 2015-03
2 | 520H7653 | 4
a
Para-
meter
-
r01
Diff.
r05
r06
r09
r10
r12
r14
A01
A02
A03
Parameter by operation via data
communication
SH / OD% / S3 temp
TempSetpoint.
Differential
Units
0: °C + bar 1:
°F + psig
(in AKM only °C + bar – is displayed –
whatever the setting).
ExtRefOffset
Adjust S2
Adjust S3
Main Switch
Therm. Mode
Hgh.TempAlrm
Low.TempAlrm
TempAlrmDel
With data communication the impor- tance of the
individual alarms can be defined. Setting is
carried out in the "Alarm destinations" menu.
DKRCI.PS.RP0.D2.0