SHE control panel TRZ Plus Comfort
Troubleshooting
All LED displays are dark (without mains 230 V/50 Hz)
• discharge totally battery, take off fuse F3 (battery) disconnect emergency batteries and wait at least 2 min. Replace by
new emergency batteries and connect them, replace fuse F3.
The green LED
is dark
OK
• Mains connection out of order.
• Mains fuse defective.
• Battery out of order.
• Battery fuse defective.
Malfunction - beep code - chart
The pulse sequence gives information regarding the source of the malfunction. The continuous acoustical signal rings
out only by SHE man. call point with buzzer and if the door contact switch is pressed.
Note: The yellow LED
OK lits up permanently during the memory checks.
Maintenance (steady flash)
The green LED
OK
- Operation OK - flashes steadily:
Reset or setting of maintenance timer by configuration-software of TRZ Plus Comfort.
For more information please see technical information of PC Software Service Port of TRZ Plus ... .
Wind-/or rain signal (steady flash)
Indicator lamp in the integrated vent switch of the TRZ Plus Comfort and/or ventilation switch LTA 25.
Open display (to last signal)
__________________________
Indicator lamp in the integrated vent switch of the TRZ Plus Comfort and/or ventilation switch LTA25. The indicator lamp
lights at ventilation function Stop or Open.
48
all OK
mains failure
battery failure
malfunction SHE manual call point
malfunction autom. detector
malfunction motor monitoring circuit
memory error
- malfunction, the red LED
Maintenance
SHE activation and the green LED
- operating
OK
02/24999539