SHE control panel TRZ Plus Comfort
Start up procedure and trial run
Test buzzer / signal light
Press red "Open"-switch
in an SHE manual call point, windows and the attached horn or signal light will be activated.
The windows will open completely, red LED-indication
.- SHE released - will glow in all SHE manual call points, the
ventilation function is inoperative. Activation of the horn / signal light will be cancelled after 3 min. SHE release will still
remain.
Completion work
Insert the glass panes in all SHE manual call points. Close the control panel door. Stick on the service contact telephone
number.
Attention: If the trial run fails, repeat the initial start up procedure!

Troubleshooting

Display - operating OK - is not shining in the SHE manual call points and the control panel:
• a malfunction has occurred (see malfunction - beep code - chart page 48), eliminate the malfunction.
• mains power connection out of order:
- check mains supply lead / voltage.
- check mains fuse.
• batteries out of order:
- check battery fuse.
- check battery connection.
- defective batteries, to be replaced.
The drives open without pressing a switch
• SHE manual call point incorrectly connected or defective, check and correct.
• automatic smoke detector soiled, replace.
• due to a fault vent switch in permanent contact.
Vent switch with reversed function
• reverse connection at the vent switch or in the control panel.
Vent switch without function
• Vent switch incorrectly connected.
• SHE activated, press Reset switch in the control panel.
• No voltage to mains supply lead, repair.
• Mains fuse defective, replace.
• Motor fuse defective, replace.
• Wind/rain alarm pending (additional module only).
Capacitance of storage batteries is inadequate for 72 h network compensational operation
The measurement of the current draw for testing the capacitance of the storage batteries has to be done in standby
mode. It may not happen directly after a motor activation. The standby mode starts automatically after approx. 3 min
when SHE-Reset is activated or after the last ventilation operation.