SHE control panel TRZ Plus Comfort
Routing of cables
Either magnetic locking 24 V DC or linear drives
Magnetic locking 24 V DC
junction box
(last junction box with monitoring diodes)
Cable type (see chapter cable length diagram)
Protective conductor cable may NOT be used!
Observe VDE regulations!
Seren 24 V AC / DC 100 mA
Mains 230 V / 50 Hz
NYM-I 3 x 1.5 mm²
Provide a separately disconnectible circuit.
Secure against unintentional switching-off.
Transmission*
Note: Make sure all cable types and specifications are according to site management requirements and the
appropriate national and local codes and laws. The stated cable cross sections must not be reduced. They are listed for
an ambient temperature of 20 °C. Increase the cross sections for higher temperatures. For E90 (E30), all cable cross
sections must be adapted to the manufacturer's specifications. All cables to the control panel (except the mains supply
lead) carry 24 V DC and must be routed separately from the mains supply lead. When routing the cables, please observe
the corresponding VDE regulations.
* with expansion via additional printed circuit board TRZ-WRMAS-Basic by TRZ Plus Comfort
34
Linear drives M9,
24 V DC, max. 1 amp
(with integrated power cut-off)
(see note)
Wind/rain detector 24 V AC / DC 100 mA*
up to 200 m IY(St) 2 x 2 x 0.8 mm
up to 350 m IY(St) 2 x 4 x 0.8 mm
Motor cluster 1
SHE call point
Vent switch
(last SHE manual
call point with end
module)
automatic alarm unit
(last alarm unit with end
module)
(see note)
(see note)
(see note)