Start up procedure and trial run

Note: The specifications for start up procedure apply to the standard functions.
Without mains voltage and without battery
Check all parts mechanically and electrically for fully tightened screw connections and damage, the terminals: plug in
connectors for motors and control elements as well as, if available, automatic detectors and wind/rain detectors.
Do not plug in the battery fuse!
With mains voltage and battery
Switch on mains. Plug in battery fuse.
Visual display on the control board
Max. 100 secs. after connecting the battery, check:
green LED
- Operation OK - lit up,
OK
red LED
- SHE activation - not lit up,
yellow LED
- Malfunction - not lit up.
Note: In case of malfunction, see chapter "Troubleshooting" and "Fault finding".
Troubleshooting
• Green LED
not lit up: Mains and/or battery and connection not OK.
OK
• Red LED
lit up: Press SHE-Reset switch in the control panel.
• Yellow LED
is flashing: - check corresponding fuses (see also malfunction - beep code - chart page 48).
- cable breakage, check cable connections.
- check if end module is missing in last smoke detector.
Vent switches
Press vent switch Open briefly, the drives open the windows completely up to end position.
The display "ventilation Open" lights up. During running: observe the windows exactly.
Attention: Make sure the drives can move freely at all times without obstruction. Pay attention to potential
collision, tension and crushing during this movement, too. Check the connection cables of the drives: they must
not be strained by tension or crushing.
Press vent switch Closed briefly, the drives close the window. The display "Ventilation Open" goes out.
Press STOP during running, STOP = press both Open and Closed switches at the same time, the drives stop. he display
"Ventilation Open" lights up.
Press vent switch Closed briefly once again, the drives close. The display "Ventilation Open" goes out.
The drives close the window completely up to end position. The display "Ventilation Open" goes out.
Attention: Pay attention to potential collision, tension and crushing during this movement, too.