Herunterladen Inhalt Inhalt Diese Seite drucken

Description Of Operating - STG-BEIKIRCH TRZ Plus Comfort Bedienungsanleitung

Rwa treppenraumzentrale
Vorschau ausblenden Andere Handbücher für TRZ Plus Comfort:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Description of operating

Manual activation in case of fire/smoke/alarm
Smoke heat extraction / opening windows
Press the red Open switch
SHE activated - is shining at all SHE manual call points, the ventilation function is out of order.
Smoke heat extraction / closing windows
Press the switch "Closed"
activated - goes out at all SHE manual call points, the ventilation function is working again.
Note: There is no Reset of the connected and activated automatic detectors!
Automatic activation in case of fire/smoke/alarm
(If automatic detectors are connected only)
Smoke heat extraction / opening windows
Smoke reaches the automatic detectors, the windows are opened completely, the red display in the automatic detector
is shining, the red LED display
out of order.
Smoke heat extraction / closing windows
Press the switch "Closed"
activated - goes out at all SHE manual call points, the yellow LED display
Note: there is no Reset of the connected and activated automatic detectors!
Reset of automatic detectors
Set the automatic detectors free from smoke by blowing out or replace them in case of heavy soiling.
Press the Reset switch on the basic circuit control board of the control panel, the windows are closing, the red display in
the automatic detectors goes out, the red LED display
yellow LED display
- malfunction - goes out, the ventilation function is working again.
Daily ventilation
(If vent switches are connected only respectively via operating element of the TRZ Plus Comfort)
Opening windows
Press the switch "Open" at the vent switch, the windows open completely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch).
Closing windows
Press the switch "Closed" at the vent switch, the windows close completely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch). In case of mains or battery
failure, the windows close immediately.
Automatic ventilation control
If activated (see start up procedure), the windows are closing automatically after xx min (10 min factory-made), in case
of mains or battery failure, the windows close immediately.
02/24999539
at a SHE manual call point, the windows open completely, the red LED display
at a SHE manual call point, the windows are closing, the red LED display
- SHE activated - is shining at all SHE manual call points, the ventilation function is
at a SHE manual call point, the windows are closing, the red LED display
SHE control panel TRZ Plus Comfort
- malfunction - flashes.
- SHE activated - goes out at all SHE manual call points, the
-
- SHE
- SHE
31