Herunterladen Inhalt Inhalt Diese Seite drucken

Possible Connections - STG-BEIKIRCH TRZ Plus Comfort Bedienungsanleitung

Rwa treppenraumzentrale
Vorschau ausblenden Andere Handbücher für TRZ Plus Comfort:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Possible connections

- linear drives 24 V DC with integrated electronic power cut-off, tandem power cut-off, synchro module or
- chain motors 24 V DC with limit switches
- overall power consumption of all motors connected max. 2 A
- 10 SHE manual call points RBH/3A... (line termination via enclosed end resistance)
- 10 automatic detectors with 2-wire-technology, optical smoke detectors and/or detectors of heat differential and/or
detectors of maximum heat or monotoring resistor ex factory via the final fuse attached
- 10 external ventilation switches "Open/Stop/Closed" (e.g. type LTA 25)
- 24 V DC siren or flashing lights, max 100 mA
- to connect 1 wind-/rain detector (e.g. type WRM 24V, WRM2) or 1 rain detector (e.g. RM, RM2)
Only with TRZ Plus Comfort or with additional module WRMAS.
- in each case one connection for potential-free report SHE activated (NO= normally Open contact) and malfunction
(NC= normally closed contact): 24V / max. 0.5 A
Only with TRZ Plus Comfort or with additional module WRMAS.
Fuse
F1 mains
* factory default, changes can lead to malfunction
02/24999539
F2 Motor
F3 battery
LED display
Fuse
SHE control panel TRZ Plus Comfort
Switch "SHE Closed" Reset
Extension ledge
DIP-Switch*
PC Service Port
Fuse battery
Battery connection
33