Fault
7.3 Display codes
Table fault codes
Fault
Cause
code
F2
The inlet fan has stopped.
F5
The outlet fan has stopped.
The temperature sensor that
measures the temperature of
the input air is defective.
F9
The appliance operates as ex-
pected, but the bypass is out of
operation.
The temperature sensor that
measures the temperature of
the output air is defective.
F10
The appliance operates as ex-
pected, but the bypass is out of
operation.
Note!
If setting 2 does not work with a mechanical rpm control device
such as a multiple switch, the RJ connector has been connec-
ted the wrong way round. Cut off one of the RJ connectors
Action user
• Contact the installer.
• Contact the installer.
• Contact the installer.
• Contact the installer.
to the rpm control and mount a new connector the other way
round .
Renovent HR Medium/Large
Chapter 7
Action installer
• Replace the inlet fan; it is defective.
• Replace the outlet fan; it is defective.
• Check the wiring from the sensor to the basic pcb.
• Check the sensor connection to the wiring.
Replace the sensor.
• Check the wiring from the sensor to the basic
pcb.
• Check the sensor connection to the wiring.
Replace the sensor.