Putting into operation
6.7.3 Adjustable settings table
De user-adjustable parameters are indicated with "U"; the in-
staller-adjustable parameters are indicated with "I" (basic pcb)
or "P"(option pcb).
Adjustable
Description
parameter
U 1
Volume step 1
U 2
Volume step 2
U 3
Volume step 3
Minimum atmospheric temperature
U 4
bypass
U 5
Minimum indoor temperature bypass
U 8
Not applicable
I 1
Fixed imbalance
I 2
No contact step
I 3
Not applicable
I 4
Switch line 1 step
I 5
Switch line 2 step
I 6
Switch line 3 step
I 7
Imbalance permissible
I 8
Bypass mode
I 9
Hysteresis bypass
I10
Constant pressure switched off
I11
Preheater
I12
Offset temperature preheater
I13
Filter message on/off
I14
Option pcb present
I15
I16
Fan off
I17
Repeat time
I18
Minimum switch-off time fan(s)
Minimum switch-off time fan(s) after
I19
switching on 230V.
For a description of these settings refer to section 6.2 and 6.3
for U1 - U8 and section 6.4 for I1 - I19.
Setting range
50..(max-10)
50..(max-5)
50..300 (Medium)
50..400 (Large)
5 .. 20
18 .. 30
0.1
-100..+100
0,1,2,3
2.3
0,1,2,3
0,1,2,3
0,1,2,3
0.1
0,1,2
0 .. 5
0.1
0, 1
-30 .. + 30
1.0
1.0
0.1
1,2,3
1 .. 24
1 .. 240
1 .. 240
The description of parameters P1 - P17 that may be displayed
are included in the installation instructions that come with the
option pcb.
Renovent HR Medium/Large
Chapter 6
Factory setting
100
Medium 150
Large 200
225 Medium
300 Large
10
22
0 (off)
0
1
2
1
2
3
1 (Yes)
1
2
0 (no)
0
0.5
1 (on)
0 (no)
0 (heat recovery)
1 (Output fan)
3 (hours)
60 (seconds)
1 (second)
23