Putting into operation
6.6 Readouts settings
As standard the current position of the multiple switch and the
connected output volume are shown (Operational mode). On
the left the position of the multiple switch (position 1, 2 or 3) is
shown and to the right of the dot the volume of the output fan
is shown.
6.6.1 Reading out settings by the user
The user can read out other relevant data using keys "+" and "-"
(step 1 to step 6). Step numbers are not shown on the display!
See the table of section 6.6.2 for user readout; when no key is
operated during 5 minutes, the display automatically returns
to operational mode. Key "+" can be used to scroll through the
menu; key "-" always takes you back to step 1. Modifying set-
tings is not possible in this situation.
6.6.2 Reading out settings by the installer
A more comprehensive readout programme is available for the
installer. Pressing keys "F" and "OK" during 3 seconds calls up
all installer data. In this menu the values cannot
Activating this menu always calls up step no. 7 (see table be-
low); pressing key "+" calls up the installer and user data and
pressing key "-" takes you back to step no. 1.
After 5 minutes this menu automatically disappears and the
display will show the operational situation again.
In the event of an error, the error code appears on the display;
see also chapter 7.
Readout
Step
(example)
number
No.1
2,200
No.2
C 0
No.3
bP.1
No.4
tP.9
No.5
tS.21
No.6
In.0
u
No.7
.156
No.8
.156
U
No.9
t.180
No.10
A.180
No.11
u0.0
No.12
St.9
No.13
Pt.18
Description
Current position/outlet volume [m
Message code operating condition
Bypass status
(only if mounted)
Temperature from atmosphere
Temperature from indoors
n.a.
Current input volume
Current output volume
Current pressure input duct
Current pressure output duct
Status frost protection
Temperature to atmosphere
(Sensor not connected as standard)
Temperature to indoors
(Sensor not connected as standard)
Renovent HR Medium/Large
>3s
Remark
3
/h]
C0 = No message
C3 = The input fan runs in constant pressure mode
C6 = The output fan runs in constant pressure mode
0 = bypass valve shut, 1 = bypass valve automatic
2 = input at minimum
[°C] At negative temperature (below 0°C) then readout tP.9.
[°C]
3
[m
/h]
[m
3
/h]
[Pa]
[Pa]
0 = none, 1 - 4 = imbalance, 5 = input fan off
[°C]
If not connected St.75
[°C]
If not connected Pt.75
Chapter 6
a = Setting the multiple switch
b = Volume output fan
21