5.  OPERATING LIMITS
If the unit is filled with cooling water, the condensation that is formed on the coil will be discharged
via the condensate drain connection. If the cooling water temperature is very low or the air humidity
is very high, condensation might form on other components than the coil. This condensation is not
collected in the condensate drain, but may drip under the unit. To prevent this, a minimum permitted
water temperature must be taken into account in function of the relative humidity and the ambient air
temperature.
Permitted minimum water temperature (°C)
40 %
50 %
60 %
70 %
RH (%)
80 %
90 %
100 %
6.  ROOM THERMOSTAT
Economy mode
Comfort mode
Temperature setting up button
Clock setting down button
Weekday
Setting button
60
AMBIENT TEMPERATURE / DRY-BULB TEMPERATURE (°C)
21 °C
23 °C
°C
°C
3
3
°C
°C
3
3
°C
°C
3
3
°C
°C
3
4
°C
°C
4
5
°C
°C
5
6
°C
°C
6
8
Fan speed adjust button
JAGA NV | BRIZA 22 - PLUG & PLAY | MANUAL | 2022.03.10 | V.1
25 °C
27 °C
°C
°C
3
3
°C
°C
3
3
°C
°C
4
4
°C
°C
5
6
°C
°C
6
8
°C
°C
8
10
°C
/
10
Permitted minimum water temperature
Current period
External sensor
Internal sensor or both
Temperature setting up button
Clock setting up button
Clock
On/off button
Mode adjust button
29 °C
31 °C
°C
°C
3
4
°C
°C
4
6
°C
°C
6
8
°C
°C
8
10
°C
/
10
/
/
/
/