The following tables describe the individual functions available in the control unit.
MENU
Automatic ascent time of bollard 1 and bollard 2.
TCA
At the end of the set time the control unit commands the bollard ascent again.
Bollard working time 1. Adjusts the maximum duration of the descent and ascent
TM1
manoeuvre of bollard 1.
It must be set about 4 seconds longer than the actual running time of the automatism.
Bollard working time. Adjusts the maximum duration of the bollard descent and as-
TM2
cent manoeuvre 2.
It must be set about 4 seconds longer than the actual running time of the automatism.
Hold time, it commands an ascent manoeuvre for approx. 3 seconds
BLC
Value expressed in hours. The value 0 disables the function.
Adjusts the stopping time after the OPEN limit switch has been intercepted.
BLco
Value expressed in tenths of a second.
Adjusts the stopping time after the CLOSE limit switch is intercepted.
BLcC
Value expressed in tenths of a second.
Sets the operating mode of auxiliary output 1
0: Contact for connection of bollard 1 status light (see AUX connection diagram).
Light on when the bollard is lowered.
Flashing light frequency 1 flash/second with bollard in descent.
Flashing light frequency 2 flash/second with bollard in ascent.
Warning light off with bollard raised.
1: AUX 1 contact closed only when bollard 1 is raised.
2: Contact for connection of siren/alarm, closed during the ascent of the bollard 1,
see connection diagram Fig.6.
Aux1
3: Output replicates the status of input LSC1
4: Output reverses the status of input LSC1
5: Light-buzzer board command output mod. CP.BL (fig.10)
6: Zone light output. The output is activated with bollard in movement or with bollard
lowered (and logic TCA=ON)
7: Traffic light output. The output is deactivated when the bollard is fully lowered
Note:
If logic PP=On the settings are relative only to bollard 1
If logic PP=off the settings are relative to both bollards.
Sets the operating mode of auxiliary output 2
0: Contact for connection of bollard 2 status light (see AUX connection diagram).
Light on when the bollard is lowered.
Flashing light frequency 1 flash/second with bollard in descent.
Flashing light frequency 2 flash/second with bollard in ascent.
Warning light off with bollard raised.
1: AUX 2 contact closed only when the bollard is raised.
2: Contact for siren/alarm connection, closed during the ascent of the bollard 2, see
connection diagram Fig.6.
Aux2
3: Output replicates the status of input LSC2
4: Output replicates the status of input LSO2
5: Light-buzzer board command output mod. CP.BL (fig.10)
6: Zone light output. The output is activated with bollard in movement or with bollard
lowered (and logic TCA=ON)
7: Traffic light output. The output is deactivated when the bollard is fully lowered
Note:
If logic PP=On the settings are relative only to bollard 2
If logic PP=off the settings are relative to both bollards.
Sets the operating mode of channel 1 of the plug-in receiver.
0: Open
1: Close
2: Step-by-Step
CH1
3: STOP.
Note:
If logic PP=On the settings are relative to bollard 1 only
If logic PP=off the settings are relative to both bollards.
14
PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
PARAMETERS (PAR)
FUNCTION
MIN-MAX-(Default)
MEMO
3-240-(10s)
1-90-(10s)
1-90-(10s)
0-12-(2)
0-20-(10)
0-20-(10)
0-7-(5)
0-7-(0)
0-3-(0)