• To use demand control on the connected units, make the settings as shown below.
(a) To use only connected unit demand control (contact input) without using Power
Save on the remote controller
Button operation
1
Unit1
Power Save
Schedule
Fan Mode
Anti-freeze
F1
(b) To use both connected unit demand control (contact input) and Power Save on the
remote controller
* Exercise control using low values in the demand control settings and Power Save control
capacity. When the contact ON and Power Save start times differ, control will be exercised as
of the earliest low value. (See the table below.)
Table: Control values when Power Save and demand control are both used
Period
Power Save value
12:00-6:30
6:30-7:00
7:00-11:30
11:30-12:00
Example) When Power Save is from 7:00 to 12:00 with a control capacity of 50%, and
Power Save time
period setting
Unit contact
input
Contact ON
Maximum
capacity used
100%
by the unit
Time
5:00
• While the contact is ON or Power Save is being applied, the maximum capacity will be limited to whichever is the lower
value of the Power Save and demand control settings.
• While the contact is OFF and Power Save is not applied, control will be exercised with the maximum capacity of 100%.
• The control capacity during periods when Power Save is not set will be 100%.
30
FRI
No
No
Normal
No
Next
F2
F3
F4
Connected unit demand
control value
– (100%)
– (100%)
– (100%)
50%
50%
– (100%)
contact is ON for the connected unit (capacity: 60%)
Power Save starts
6:00
7:00
In the Operation setting screen, press the [F1]
button to move the cursor to Power Save.
Press the [F3] button to select "No".
* Refer to the connected unit Instruction Book for
details on connected unit demand control.
* Do not set the Power Save settings on the remote
controller. Refer to the connected unit Instruction
Book for details.
Control value
actually used
100%
60%
60%
50%
8:00
9:00
10:00
→ Because Power Save is set from
50%
7:00, control begins based on the
50%
Power Save setting.
50%
Power Save ends
Contact OFF
11:00
12:00
100%
13:00