Pressure gauge.
Expansion vessel.
Buffer tank.
Electrolytic sleeve.
Flexible
hose
for
hydraulic
connection with a water passage
section equal to or greater than
the section of the boiler intakes
and
resistant
to
temperatures of 110 °C
4.12. Do not install the boiler in a sleeping room.
4.13. Install a fire protection between the ground and the stove if the floor is a combustible material.
4.14. Security distances should be respected when the stove is installed in spaces where materials around it, be it
the construction material itself, the fuel or any other type of materials, are likely to be flammable. Ensuring a
better access to the stove for future maintenance or repair work is also worth considering.
A
Lateral wall.
VAP30 back of the stove. Minimum
B
separation that allows visualizing the
label marking the stove.
VAP24 back of the stove. Minimum
B
separation that allows visualizing the
label marking the stove.
VAP5-20 back of the stove. Minimum
B
separation that allows visualizing the
label marking the stove.
C
1.5 x depth of stove.
D
Shelf.
E
Depth of stove.
4.15. Gas output must be located in a ventilated area, not in closed or half-closed areas e.g. garage, corridor, air
space of the house or places where gas may concentrate.
4.16. The external parts of the boiler may reach high temperatures that might burn when touching; it is
recommended to use a non flammable grid to avoid risk of burn for children and old people.
The end of the gas outlet flex should remain higher than the boiler's output. It is mandatory to install at
least two metres in length vertically to create natural current preventing smoke, odors or eventual cut of
electric supply.
The horizontal pipe must not be longer than 1 metre; greater lengths mean ash, condensation or corrosion
may build up in this area.
RECOMMENDABLE
MANDATORY
MANDATORY
RECOMMENDABLE
RECOMMENDABLE
constant
LOCATION AND SAFETY DISTANCES.
≥ 830 mm
≥ 110 mm
≥ 100 mm
See dimensions
≥ 400 mm
See dimensions
SECURITY NORMS FOR GAS OUTPUT AND AIR INPUT.
• To compare the pressure of the circuit with
which the boiler indicates.
• If the boiler's expansion tank is not big enough
according to specific calculations.
• Installation of special features such as radiant
floor, areas operated by thermostatic valves or
independent thermostats, other boilers working
in the same site, etc. The device must be fitted
with a buffer tank for proper regulation.
Between 20 and 30L per kW
• Depending on the material used for the hydraulic
circuit.
ALL.
≥ E
46
Drawing 5