7. Configuration
7.1 First control level
Parameterisation of the set point
The set point, S1, is directly selectable by pressing the SET key. By then
pressing the UP or DOWN keys it can be set.
Parameters Functional description Setting range Standard
EN
S1
7.2 Second control level (P parameter)
Setting of control parameters
By pressing the UP and DOWN keys simultaneously for at least
4 seconds one reaches the parameter list for control parameters
(beginning with P0).
The UP key scrolls the list up, the DOWN key scrolls it downwards. If one
presses the SET key, the value of the respective parameter is displayed.
By then pressing the UP or DOWN keys the value is adjusted.
After releasing all the keys, the new value will be stored permanently. If,
during 60 seconds, no key is pressed, there is an automatic return to the
initial position.
Parameters Functional description Setting range Standard
P0
P2
P4
1)
P5
1)
P6
P19
P30
P31
P32
16
Set point, control contact 1
Actual value
Hysteresis K1
Lower set-point limit
Upper set-point limit
Actual value correction
Key lock
Lower alarm limit
Upper alarm limit
Hysteresis for alarm function
WIKA operating instructions models SC58, SC64
P4 ... P5
-
0.1 ... 99.9 K
-99 °C ... P5
P4 ... 999 °C
-20.0 ... +20.0 K
0: not locked
1: locked
-99 ... 999 °C
-99 ... 999 °C
0.5 ... 99.9 K
setting
0.0 °C
setting
-
1.0 K
-99 °C
999 °C
0.0 K
0
-99 °C
999 °C
1.0 K