Network interface
Installation
Fasten the module with 2 M6 screws and a tightening
torque of 3 Nm using the mounting holes.

Electrical connection

Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
► Fuse the power supplies for sensors and actuators
separately.
► Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
For UL: Observe cable requirements and power
supply requirements (see chapter
UL requirements)!
– Establish power supply of sensor/bus and
actuator via a separate power source if possible.
– Due to the galvanic isolation of BNI PNT-538-...,
devices without galvanic isolation such as the
BNI PNT-508-105-Z067 must not be supplied
with the same power
– The total current for the sensor and actuator
supply must not exceed 16 A each.
www.balluff.com
source.
Electrical connection (continued)
BNI PNT-5_8-105-Z067
M12 plug
(L-coded, with FE)
BNI PNT-5_8-105-Z077
M12 plug
(L-coded, without FE)
Top view of M12 plugs (left) and sockets (right)
Pin
Signal
1
+24 V US
2
GND UA
1)
3
GND US
4
+24 V UA
FE
n.a.
FE
GND: Pin 2 and Pin 3 are galvanically isolated on variants
1)
BNI PNT-538-...
M12 socket
(L-coded, with FE)
M12 socket
(L-coded, without FE)
Description
Module/sensor
voltage
N24
Actuator supply
Sensor supply
P24
Actuator supply
n.a.
Function ground
english