Herunterladen Inhalt Inhalt Diese Seite drucken

Balluff BNI PNT-508-105-Z067 Montageanleitung Seite 8

Vorschau ausblenden Andere Handbücher für BNI PNT-508-105-Z067:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BNI PNT-5_8-105-Z0_7
Network interface
Construction and function
FE connection
PROFINET Port 1
Power supply input
Port 0
Port 2
Port 4
Port 6
The Profinet IO-Link master is a decentralized and
configurable gateway that processes and evaluates the
input and output signals of standard sensors and actuators
as well as process data from connected IO-Link devices.
The data is transmitted via an existing fieldbus interface to
a higher-level controller set up by the user for further
processing.
A web server is available on the IO-Link master for
configuration and diagnostics.
Display elements
Port/Pin LEDs
LED 00 – Port-pin 4
LED 01 – Port-pin 2
2
english
Mounting hole
PROFINET Port 2
Power supply
output
Port 1
Port 3
Port 5
Port 7
Mounting hole
Status LEDs
Port/Pin LEDs:
Status of IO-Link and
I/O-Ports
Display elements
Port/Pin LEDs Standard-Port
Display
Meaning
Off
State of input or output pin is 0
Yellow
State of input or output pin is 1
Both LEDs
Short circuit of sensor supply between
flashing red
pin 1 and pin 3
Red
Short circuit at output on pin 2/4 against
pin 3
Red
No high signal at diagnostic input
Red
24 V input signal on configured output
(actuator warning)
Port/Pin LEDs IO-Link-Port
Display
Meaning
Green
IO-Link connection active
Flashing
No IO-Link connection or incorrect
green
IO-Link device
Green, fast
IO-Link: Preoperate during data storage
flashing
Red, fast
Validation failed / incorrect configuration
flashing
of the IO-Link data length
Red, fast
Data storage failed / incorrect device for
flashing
data storage
Red
IO-Link: Short circuit of pin 4 against
pin 3
Status LEDs
LED
Signal
Meaning
US
Green
Input voltage OK
Red flashing
Input voltage low (< 18 V)
UA
Green
Output voltage OK
Red flashing
Output voltage low (< 18 V)
Red
No output voltage present
(< 11 V)
SF
Off
No error
Red
Watchdog timeout; channel,
general or extended diagnostics
present; system error
Red flashing
Service DCP signal started via
bus
BF
Off
No error
Red
Low speed of physical link; or no
physical link
Red flashing
No data exchange or no
configuration
100
Off
Transmission rate: 10 Mbit/s
Yellow
Transmission rate: 100 Mbit/s
XF1/2 Flashing
Data transfer
green

Werbung

Inhaltsverzeichnis
loading