Circuit Diagrams

A1
A1
13 23 33
S11
S12
S13
K1
S14
S41
S42
K2
S43
S44
A2
14 24 34
A2
BL 5903.03
A1
A1
13 23 31
S11
S12
S13
K1
S14
S41
S42
K2
S43
S44
A2
14 24 32
A2
BL 5903.22

Connection Terminals

Terminal designation
A1+
A2
S12, S14, S42, S44
S11, S13, S41, S43
13, 14, 23, 24, 33, 34
31,32
S11 S13
S12 S14
13 23 33
S41
14
24 34
S42
S44
S43
M8087_a
S11 S13
S12 S14
13 23 31
S41
14 24 32
S42
S44 S43
M8088_a

Signal description

+ / L
- / N
Inputs
Outputs
Forcibly guided NO contacts for
release circuit
Forcibly guided NO contacts for
indicator signal

Technical Data

Input
Nominal voltage U
:
N
Voltage range:
at max. 5 % residual ripple:
Nominal consumption:
Nennfrequenz:
Control voltage over
S11, S13, S41, S43:
Control current over
S12, S14, S42, S44:
Min. voltage at
terminals S12, S14, S42 S44: DC 16 V
Short circuit protection:
Output
Contact
BH 5903.03:
BH 5903.22:
Operate delay typ. at U
:
N
Manual start:
Automatic start:
Release delay typ. at U
:
N
Disconnecting the supply:
Disconnecting S12, S22:
Contact type:
Output rated voltage:
Switching of low loads:
Thermal current I
:
th
Switching capacity
to AC 15:
NO contact:
NC contact:
to DC 13 at 0.1 Hz:
Electrical life
to AC 15 at 2 A, AC 230 V:
Permissible switching
frequency:
Short circuit strength
max. fuse rating:
line circuit breaker:
Mechanical life:
General Data
Operating mode:
Temperature range
Operation:
Storage:
Altitude:
Clearance and creepage
distances
Rated impulse voltage /
pollution degree:
EMC
Electrostatic discharge:
HF-irradiation
80 MHz ... 2.7 GHz:
Fast transients:
Surge voltages
between
wires for power supply:
between wire and ground:
HF-wire guided:
Interference suppression:
14
BH 5903
BL 5903
DC 24 V
AC 24, 110, 230 V
-
0.8 ... 1.1 U
N
0.85 ... 1.15 U
-
N
Max. 170 mA
Max. 7 VA
-
50 / 60 Hz
Pulses max. 23 V at U
N
Each 4.5 mA at U
N
Internal with PTC
3 NO contacts
2 NO, 1 NC contacts
(only to be used as monitoring contact)
Max. 45 ms
Max. 800 ms,
if voltage failure > approx. 150 ms
Max. 7 s,
if voltage failure < approx. 150 ms
Max. 18 ms
15 ms
Relay, forcibly guided
AC 250 V
DC: see continuous limit curve
≥ 100 mV
5 A
3 A / AC 230 V
IEC/EN 60947-5-1
2 A / AC 230 V
IEC/EN 60947-5-1
8 A / DC 24 V
IEC/EN 60947-5-1
10
5
switching cycles IEC/EN 60947-5-1
max. 1200 switching cycles / h
6 A gG / gL
IEC/EN 60947-5-1
C 8 A
10 x 10
switching cycles
6
Continuous operation
± 0 ... + 50 °C
- 25 ... + 85 °C
≤ 2000 m
4 kV / 2 (basis insulation) IEC/EN 60664-1
8 kV (air)
IEC/EN 61000-4-2
10 V / m
IEC/EN 61000-4-3
2 kV
IEC/EN 61000-4-4
1 kV
IEC/EN 61000-4-5
2 kV
IEC/EN 61000-4-5
10 V
IEC/EN 61000-4-6
Limit value class A*
EN 55011
)
*) The device is designed for the usage
under industrial conditions (Class A,
EN 55011). When connected to a
low voltage public system (Class B,
EN 55011) radio interference can be
generated.
To avoid this, appropriate measures
have to be taken.
BH 5903, BL 5903 / 26.01.21 en / 297A