Herunterladen Inhalt Inhalt Diese Seite drucken

CARLO GAVAZZI PD30ETB BP IO Serie Betriebsanleitung Seite 23

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 46
b) Enter the maximum time the Gap will be present in the menu "Object and Gap monitor" -> "Gap
maximum time" between 10 ... 60 000 ms (default value is 500) ms, e.g. 130 ms.
As a help the gap time can be read from the "Object and Gap monitor" -> "Gap time".
11) The sensor is now ready to use.
12) The Parameter for Object length will toggle between: Measurement running and Inside limits, Time
too
long or, Time too short.
13) The Parameter for Gap length will toggle between: Measurement running and Inside limits, Time too long
or, Time too short.
Standalone operation in SIO Mode
14) Disconnect the sensor from the SCTL55 or IO-Link master.
15) Output Pin 4 will activate of the object time is too long or too short.
16) Output Pin 2 will activate of the gap time is too long or too short.
NB! If the signals of both outputs are evaluated using a logical OR function, the output of this OR
function can be used as a common error output for both Object and Gap.
Rev.00 - 06 .2021 | MAN PD30ETB IO-Link EN | © 2021 | CARLO GAVAZZI Industri
23

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis