9.2

Systemfehlermeldungen

Code
Description
A102
checksum error
general reset & new
calibr.required
W103
initialising - please wait
A106
downloading please wait
A110
checksum error
general reset & new
calibr.required
A111
electronics defect
A113
electronics defect
A114
electronics defect
A115
electronics defect
A116
download error
repeat download
A121
electronics defect
W153
initialising - please wait
A155
electronics defect
A160
checksum error
general reset & new
calibr.required
A164
electronics defect
A171
electronics defect
A231
sensor 1 defect
check connection
W511
no factory calibration ch1
A512
recording of mapping please
wait
A601
linearisation ch1 curve not
monotone
W611
less than 2 linearisation
points for channel 1
W621
simulation ch. 1 on
Possible cause
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
2
E
PROM storage not yet finished
processing data download
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
RAM defective
RAM defective
2
E
PROM defect
general hardware problem
checksum of stored data not correct
no factory calibration existant;
EPROM defective
initialisation of electronics
hardware problem
device has been powered off before data
could be stored;
emc problem;
2
E
PROM defect
hardware problem
hardware problem
HF module or electronics defective
factory calibration has been deleted
mapping active
linearisation not monotonously increasing correct linearisation table
number of entered linearisation points < 2 correct linearisation table
simulation mode is active
Störungsbehebung
Remedy
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
wait some seconds; if warning
prevails, exchange electronics
wait until warning disappears
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
restart download of data
contact service
wait some seconds; if warning
prevails, power off device and
power on again
reset;
if alarm prevails after reset,
exchange electronics
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics
exchange HF module or electronics
record new factory calibration
wait some seconds until alarm
disappears
switch off simulation mode