3. QUICK START

3.1. Quick Start ATyS g M (2P)
quick start
EN
ATyS
g
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
Packaging and contents are in good condition.
n
The product reference corresponds to the order.
n
Contents should include:
n
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
This product must always be installed and commissioned
n
by qualified and approved personnel.
Maintenance and servicing operations should be
n
performed by trained and authorised personnel.
Do not handle any control or power cables connected to
n
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
Always use an appropriate voltage detection device to
n
confirm the absence of voltage.
Ensure that no metal objects are allowed to fall in the
n
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
In case the product is dropped or damaged in any way it
n
is recommended to replace the complete product.
Accessories
Bridging bars and 125A or 160A.
n
Control voltage transformer (400Vac -> 230Vac).
n
Voltage sensine and power supply TAP.
n
Terminal shrouds.
n
Additionnal aux contact block.
n
Polycarbonate enclosure.
n
Polycarbonate extension box.
n
Power Connection Terminals.
n
Sealable cover.
n
www.socomec.com
www.socomec.com/operating-instructions
To download, brochures, catalogues and technical manuals.
Printing informations: 1 color Black. White paper 90g/m
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
CORPORATE HQ CONTACT:
SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE
542955E
8
DE

Installation and Commissioning

40 - 160A (2P)
M
STEP 1
Cabinet / Back
Plate Installation
STEP 3
Type
Inputs
Outputs O1: 63 / 64
2
.
Non contractual document.
Subject to change without notice.
STEP 2
STEP 3
Connecting the
CONTROL /
POWER section
AUX POWER
terminal
connections
CONTROL / AUX POWER Terminals and wiring
Status of the
Terminal no.
Application
contact
I1: 207 / 208
Network/Network
Network-Genset.
I1: 207 / 209
Network/Network
Network-Genset.
I3: 207 / 210
Network-Network or
Network-Generating
set
Network-Network or
Network-Generating
set
O2: 73 / 74
Network-Genset.
Automatic Operation
STEP 4
STEP 5
CHECK
Programming
2 clips de verrouillage
Output
Description
characteristics
With priority
Without priority
Dry potential free
contact
Automatic retransfer
Manual Retransfer
Source priority 1
Source priority 2
Dry potential free
contact
Stop the test on load
Test on load
AUTO mode
Dry potential free
contact
Automatic mode inhibition
Product not available :
Resistive load
- Manual mode
2A 30 Vdc
- Command default
0.5A 230Vac
- Electronic default
Pmax : 60W or 125VA
- No source
Umax : 30Vdc or
230Vac
Product available
Resistive load
No start command genset
2A 30 Vdc
0.5A 230Vac
Generating set starting
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
ATyS g M – 542933D – SOCOMEC
STEP 6A
STEP 6B
Emergency Manual
Operation
STEP 6C
Padlocking
2 clips de verrouillage
OK
OK
Recommended
connection
cross-section
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Type
Auxiliary
block
1309 10
Auxiliary
block
1309 10
OK
OK
S