Primary Device Functions (continued)
Safe state of outputs
Setting the safe states of the outputs. The outputs
automatically assume the state of the configured safe state
if IO-Link communication is interrupted or the Process
Data Output Invalid flag is set.
Value
Meaning
00
Output is switched off (0V)
01
Output is switched on (+24V)
10
Current state is maintained
11
Not valid
Tab. 4-8:
Configuration of digital inputs and outputs – ISDU: Safe
state of outputs, configuration
Bit-Mapping
Byte 0
Bit 7...2
Bit 1
Bit 0
Subindex 1
Byte 4
Bit 7...2
Bit 1
Bit 0
Subindex 5
Tab. 4-9:
Configuration of digital inputs and outputs – ISDU: Safe
state of outputs, bit-mapping
With variant 1, the pin 2 values are always 0x00.
Default value
0x0000000000000000 – If an error occurs in the IO-Link
communication, the outputs are switched off.
16
english
Byte 1
Bit 7...2
Bit 1
Bit 0
Subindex 2
Byte 5
Bit 7...2
Bit 1
Bit 0
Subindex 6
Byte 2
Bit 7...2
Bit 1
Bit 0
Subindex 3
Byte 6
Bit 7...2
Bit 1
Bit 0
Subindex 7
Byte 3
Bit 7...2
Bit 1
Bit 0
Subindex 4
Byte 7
Bit 7...2
Bit 1
Bit 0
Subindex 8