SYSTEM PARAMETERS

Note: Some parameters may vary depending on your system.
System address. (Not available on systems with BACnet gateway). This allows you to define
the number of the system in your installation. By default, it displays the value 1. The system
will show the free address values with a maximum value of 99.
Temperature range. This allows you to select the maximum temperature for heating mode
EN
(19-30°C) and minimum temperature for cooling mode (18-26°C), in steps of 1°C. If you want,
you can disable any of the modes. By default, the maximum heating temperature is set to
30°C and the minimum cooling temperature to 18°C.
Standby mode. (Only for Airzone Blueface thermostats). Configuration of the operation
logic of the motorized elements when there is no demand on the system. This is disabled by
default.
Relay settings. This allows you to change the operation logic of the main control board's
CMV/Boiler relay. By default, it is set to CMV.
Q-Adapt. (Only for Airzone Think thermostats.)
1.
In direct expansion units. This allows you to define the airflow control algorithm that
best fits the duct installation. The options available are:
- Maximum: The system operates at maximum speed regardless of the number of zones.
- Power: The system operates at a higher speed than in Standard mode to ensure airflow
is increased.
- Standard (by default): The system changes speed depending on the number of zones.
- Silence: The system operates at a lower speed than in Standard mode to improve noise
reduction.
- Minimum: The system operates at minimum speed regardless of the number of zones.
2.
In fancoil units 0-10V. This allows you to set the minimum (1.5V by default) and
maximum (10V by default) working voltage of the fan of the controlled AC unit, in 1V
steps. The minimum voltage will correspond to the desired minimum speed of the AC
unit and the maximum voltage will correspond to the maximum speed. The average
speed will correspond to the midpoint between the two.
Radio channel. This allows you to enable/disable the system's wireless association channel.
Information. (Only for Airzone Think thermostats). This allows you to display information
about:
- Zone: firmware, zone, association, actuator or communications status.
- System: firmware, settings and information on system and installation controllers.
- Devices: indicates the elements connected to the system.
- Webserver: firmware, IP address, gateway, MAC and PIN.
Reset system. (Only available for Airzone Blueface master thermostats). This allows you to
reset the system by returning it to factory settings. To reconfigure the thermostats, go to the
Initial configuration section.
Centralized control. This allows you to define whether or not your installation has a
centralized controller. By default, it will be configured as deactivated.
18