Airflow Regulation

Important: Start the airflow adjustment from the central dampers and finalize at damper no. 1.
EN

AIRFLOW ADJUSTMENT (REG)

1.
Turn on and generate demand in all the zones to open all the dampers.
2.
Turn off the zone/damper to be adjusted.
3.
Adjust the desired maximum opening with the REG lever (I/II/III/IV).
4.
Turn on the zone and verify that the airflow is correct.

MINIMUM AIR ADJUSTMENT (A-M)

1.
Turn on and generate demand in all the zones to open all the dampers.
2.
Adjust the desired minimum opening with the A-M lever (a/b/c/d).
3.
Turn off the zone and verify that the minimum airflow is correct.
A-M
16
REG
Damper opening angle