Thermostat installation
1.
Remove the back of the thermostat.
2.
Fix the back of the thermostat to the
wall.
3.
Connect the main control board to any
of the three terminals AZ1, AZ2 o AZ3.
Fix the cables using the main control
board turrets.
EN
If
your
thermostat, insert the CR2450 button
battery.
4.
Place the display over the fixed support.
5.
Place the anti-vandalism rods (optional)
to better hold the thermostat in place.
Connection to the indoor unit
1.
Disconnect the power supply of the Daikin indoor unit and the Airzone system.
2.
Find the P1 P2 connection of the Daikin indoor unit (where the thermostat is connected).
3.
Connect the Airzone Gateway to the P1 P2 port of the Daikin unit using the cable supplied
by Airzone.
4.
Power the Daikin indoor unit and the Airzone system. Check the gateway LEDs (see self-
diagnosis section).
5.
Disable the Setback function using the Daikin controllers (BRC1E52A7, ...) for a proper
operation of the Airzone system. Service Settings > Field Settings > 1e-2-01. If you have any
doubt, please check the Instruction manual Daikin BRC1E52A7.
8
thermostat
is
a
wireless
AZ1-AZ2-AZ3
AZ1-AZ2-AZ3