6.2.3 Ethernet Connection via Patch Panel with Screw Terminals
1
2
3
Legend
1
= Plug-in jumper for shielding
earthing selection
2
= Screw connection terminals
for field wiring
3
= EN mounting rails
a
a = 10 mm
b = 35 mm
c = 5 mm
▶
Remove cable sheath corresponding to the length b.
▶
Move the braided screen 10 mm backwards over the outer jacket.
▶
Remove the aluminium foil.
▶
Strip the single cores by 5 mm.
▶
Lay the shielding under the clamp bracket on the strain relief and screw it down.
▶
Connect all single cores to the screw connection terminals. Keep the single cores twisted
up to the connection terminals if possible.
284189 / 985160310020
2021-07-20·BA00·III·en·02
4
1
Ø
1 4
2 5
5
3 7
6 8
6
b
c
Mounting and Installation
4
= RJ45 socket (TP port)
5
= Universal snap foot for
EN mounting rails
6
= Strain relief with shielding
connection