Herunterladen Inhalt Inhalt Diese Seite drucken

Ecoflam MAX P 15 AB LN CONFORT 100 Bedienungsanleitung Seite 8

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 66
EN
Function
- General safety functions
Operating function
- If heat is requested by the boiler
thermostat, the automatic oil
combustion control unit starts the
program sequence.
- The motor starts, the igniter is switched
on and the preventilation period of 15
seconds commences.
- During the preventilation period, the
furnace is monitored for flame signals.
- At the end of the preventilation period,
the fuel-oil solenoid valve opens and the
burner starts.
- The igniter remains switched off while
the burner is in operation.
Controlled shutdown
- Boiler thermostat interrupts heat
request.
- The fuel-oil solenoid valve closes and
the flame is extinguished.
- Burner motor switches off.
- Burner enters standby.
105
8
www.ecoflam-burners.com
Safety function
A safety shutdown occurs:
- if a flame signal is present during
preventilation (parasitic flame
monitoring).
- if no flame is produced within 5 seconds
(safety time) of start-up (fuel
authorisation).
- if no flame is produced after an
unsuccessful restart attempt in the
event of flame failure during operation.
A safety shutdown is indicated by the
malfunction lamp lighting up and it is then
only possible to reenable the burner by
pressing the reset button after the cause
of the malfunction has been rectified.
For further information, see the
automatic combustion control unit
description.
101
103
HS
M
M1
106
Y1
104
102
Y2
104
T1
118
M1
Burner motor
HS
Hydraulic system
T1
Ignition Transformer
Y1
Solenoid valve
Y2
Solenoid valve
101
Blower / Fan
102
Oil pump
103
Air damper
104
Oil pressure regulator
105
Hoses
106
Filter
118
Nozzle
420011136900

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Max p 15 ab ln sp110Max p 20 ab ln sp235

Inhaltsverzeichnis