SetupSequence(continued)
All manuals and user guides at all-guides.com
Analogue
Output type
Analogue output
range
Output action
Calibrate
Output?
•Installation
These units must only be installed by qualified staff in accordance with
the information given in this manual and all relevant national electrical
wiring and safety rules must be followed.
Locate the instrument in an area that is free from dust, moisture and
corrosive gases.
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 12-28 AWG Cu Wire rated for temperatures above 0 °C Only,
tighten to . lb-In. Strip wires to  mm from the ends. Use a suitable
ferrule for multi-stranded wires (do not solder).
Terminal
Signal
1
12 V DC (out)
2
Pull Up/Down
3
0V
4
Signal +
5
Signal −
6
High voltage Signal +
20
Current based output
OP=I
Voltage based output
OP=E
Output low value
OPL=
e.g., 4.00
4. 0 0
Output high value
OPH=
e.g., 20.00
20. 0 0
Direct
OP=d
Reversed
OP=r
Skip output calibration
COPn
Calibrate outputs
COPy
Analogueoutputs
Input signal/sensor
Toggle
Accept
-
-
Next
Dec
Inc
Accept
-
-
-
Next
Dec
Inc
Accept
Toggle
Accept
Toggle
Accept