Reviewingthesetup
All manuals and user guides at all-guides.com
Å
ì
For review mode, press the
and
keys simultaneously.
Press the
Å
and
ì
keys to move through the setup sequence (see
table). Greyed items in the setup table are not shown in review mode.
A 10 s timeout applies for review mode or you can press to quit.
Note: You can use review mode while the instrument is in service and
the analogue output and alarms will continue to operate correctly.
Changingthesetup
Å
ì
For setup mode, connect the security link and press the
and
keys simultaneously. The software version will be displayed (flashing). If
you wish to continue, press within 10s.
Å
ì
During setup the
and
keys change values and toggle options.
The key accepts changes and moves to the next item in the setup
sequence (see table).
Note: If you remove the security link before the end of the setup
sequence, any changes you have made will not be saved.
Clearingtrippedalarms
You can acknowledge a tripped alarm by simply pressing the key for
that channel ( ï for Alarm 1 or ENT for Alarm 2).
Displayingthealarmsetpoints
To check a setpoint, simply press the key for that channel ( ï for Alarm
1 or ENT for Alarm 2). If the alarms are disabled the display will show
---- .
16