Read the guidelines on preventing electrical interference (refer to the manual, Section 3.3).
Note
The supply chassis of the I/O must be connected to the supply chassis of the evaluation
unit.
Note
The DC load power supply must meet the following requirements:
Only low voltage less than or equal to 24 V DC safely isolated from the power supply
network must be used for the load current supply. Safe isolation can be implemented, for
example, by adhering to the specifications in VDE 0100-410 / HD 384-4-41 S2 / IEC 60364-
4-41 (as functional extra-low voltage with reliable isolation) or VDE 0805 / EN 60950 / IEC
60950 (as safety extra-low voltage (SELV)) or VDE 0106 Part 101.
Interface Pinning of the Evaluation Unit
Cables with prefitted connectors are supplied for the other interfaces. You will find the
pinning of the interfaces in the manual, Appendix A.4.
Power supply of "IN DC 24V" (pin)
Connector
Name
Function
1
+24V
24 V power supply
2
+24V
24 V power supply
3
M
Ground
4
M
Ground
RS-232 Interface, Floating "RS232" (pin)
Connector
Name
Function
Casing
Shield
Shield
2
RxD
Receive:
3
TxD
Transmit:
5
M
Ground
4
All manuals and user guides at all-guides.com
I/O Interface "DI/DO" (socket)
Connector
1
2
3
4
5
6
7
8
9
10
Direction
Wire Color
-
red
11
-
orange
-
black
-
brown
12
13
14
Direction
-
Input
Output
-
15
Name
Function
DISA
Disable: Disable manual control panel input, model
selection and training via digital I/O
SEL0
Select 0: Model selection: bit 0
/
train background
SEL1
Select 1: Model selection: bit 1
/
train view A
SEL2
Select 2: Model selection: bit 2
/
train view B
SEL3
Select 3: Model selection: bit 3
/
quality limit/calculate limit value
the vertical deviation automatically
TRN
Train: train new model
TRG
Trigger: An evaluation is started on the positive-
going edge
RES
Reset: Reset error
IN_OP
In Operation:
1 = SIMATIC VS 110 functional, no error
0 = error message.
TRD
Trained:
1 = selected model has been trained
1 = acknowledgment signals during training (RDY=0)
0 = selected model has not been trained
0 = training active
RDY
Ready:
1 = SIMATIC VS 110 in the run mode
0 = device starting up
0 = SIMATIC VS 110 in the stop mode
OK_A
Result of evaluation: Correct test object recognized
in view A.
OK_B
Result of evaluation: Correct test object recognized
in view B.
N_OK
In the "RUN" mode (evaluation): Result of evaluation
"Not OK" (signal length depends on the width of the
test object and conveyor speed)
In the "STOP" mode: set to 0
If group error occurs or during training
External trigger:
The N_OK digital output is set to "1" for the
duration of the set pulse time.
Automatic trigger:
The N_OK digital output is always set to "1"
and is permanently active.
-
-
Vision Sensor SIMATIC VS 110 - Installation Instructions
Direction
Wire
Color
Input
black
Input
brown
Input
green
Input
orange
Input
yellow
Input
red
Input
blue
Input
violet
Output
white-
black
Output
white-
brown
Output
white-
green
Output
white-
orange
Output
white-
yellow
Output
white-red
-
-
A5E00162492-01