Herunterladen Inhalt Inhalt Diese Seite drucken

Accessories; Emergency Manual Override / Stroke - GF DIASTAR DN65 Bedienungsanleitung

Membranventil pneumatisch
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Instruction manual

7 Accessories

7.1 Emergency Manual Override / Stroke

Visual position indicator
a)
b)
Threaded bush
c)
Locknut
Installation and Adjustment for Full Stroke
1.
Put valve in position <open> with control pressure (FC, DA).
2.
Remove indicator cap and indicator pin from the basic version (see Section 2).
Attention: indicator pin has left thread)
3.
Screw threaded bush with 19 mm wrench tightly into the actuator.
4.
Screw locknut on threaded bush and secure with a 41 mm wrench.
5.
Guide indicator pin through threaded bush, screw into spindle nut and secure with a 6
mm Allen wrench. (Indicator pin has left thread).
6.
Screw indicator cap onto locknut.
Adjustments
1. Minimum Flow Adjustment
(DN65-DN80, FC, FO, DA)
Put valve in position <open> using the control medium (FC, DA).
Remove locknut with a 41 mm wrench and turn the threaded bush with a 19 mm
wrench in a counter clockwise direction until the desired position is reached.
The stroke limit setting can be determined by comparing the position of the threaded
bush to the basic setting.
Tighten locknut.
Indicator pin
d)
Spindle nut
e)
Accessories
35