5. Installing the Condensing Unit Continued
C.
Provide a one-inch pitch in suction and liquid line toward the evaporator for every 10
feet of run to prevent any refrigerant that condenses in the suction line from flowing to
the compressor or when the unit is off.
D.
Mount system on concrete slab outside above average snow fall heights. Unit can
also be mounted to side of house or within a large indoor crawl space, attic, or me-
chanical room that is at least three (3) times the size of the cellar.
E.
Prevent dips, sags, or other low spots that will trap refrigerant oil.
F.
Evacuate and leak test indoor unit suction and liquid lines by purging the dry air
charge from the unit by opening the liquid line shut-off valve or removing the liquid
line outlet fitting or plug, whichever is applicable for your unit.
G.
Pressurize and leak test system (the condensing unit comes pre charged). A pressure
equal to the low side test pressure marked on the unit nameplate is recommended for
leak testing.
H.
Evacuate the system to hold at 500 microns and break the vacuum with refrigerant.
Charge the system with the correct amount of refrigerant and mark the amount, with a
permanent marker in the space provided on the unit nameplate. (See chart on below)
I.
See the full Wine Guardian Operations and installation manual for comprehensive
charging procedure.
MODEL
LIQUID LINE
CS025
1/4 inch
CS050 / WGC60
1/4 inch / 0.635 cm
SUCTION
(OD)
LINE (OD)
3/8 inch
1/2 inch / 1.27 cm
6.
Wiring the Unit for Power
A.
Connect line power to the contactor inside the condensing unit
as shown.
B.
Run 24 volt low voltage signal wires from Y and C terminals on
fan coil to Y and C connections in condenser housing (shown in
image to the left).
C.
Turn on power to the condensing unit 24 hours prior to system
start-up to allow crankcase heater to warm up compressor.
*See page 20 in
Inside of condensing unit also contains schematic.
7.
Turn Unit On
A.
Turn on power to the Fan-coil. Press the "On/Off" button on the
Remote User Interface. The Remote User Interface is preset to a
room temperature of 55°F (13°C).
B.
Press the "Up" arrow once. The display will show the existing tem-
perature setpoint. Press the "up or down" arrow buttons to adjust
the temperature to the desired setpoint.
C.
The system will turn on after a 5-minute time delay and the cold air
section will start to deliver cold air. Contact Air Innovations if the
system fails to turn on.
MODEL
Add 0.5 oz per additional linear foot of run
While checking sight glass and referring to
charging related tables and text in full O&M
All CS
16oz
Models
All WGC
0.45 kg
Models
owners manual
5
FACTORY HOLDING CHARGE
for 025/40 and 050/75 models
for full wiring schematic.