fan must be capable of breaking live voltage
contact on all switching poles to fully isolate the
fan from power during Category III overvoltage
conditions, in accordance to applicable electrical
engineering regulations.
• The device is designed for installation at a
substantial height, i.e. 2.3 m above the oor. The
fan shall only be installed in a position and an
orientation speci ed in the Operating Manual,
given the necessary entry of the power cable into
the fan housing.
• Before servicing the device, isolate it from the mains voltage with the circuit breaker. Secure the circuit breaker
against inadvertent operation.
• The fan installation design must prevent reverse ow of ue gas into the room from open ue gas exhaust
ducts and appliances operated with open ames.
• Never attempt to modify or alter the device without authorization.
• Before installing the fan, verify the load bearing capacity of the installation substructure. Improper installation
fastening may result in damage or failure of the fan and hazards to the people nearby.
The device may become dangerous if it is misused or installed by an untrained personnel.
Scope of use and work conditions
• The recuperator is intended for pumping of normal air or air containing some dust (the size of particles < 10 m),
with low aggression and humidity levels, in a temperate climate.
• The device may be used only if installed permanently, inside a building and if lack of access to the power
supply cable is ensured.
• Acceptable work temperature scope of the device: from -20°C to +40°C.
• The device in compliant with IPX4 protection level, electricity protection class: II.
• The tool should be used only in accordance with its intended purpose and in accordance with the marking on
the rating plate.
• The fan should be connected with the xed electric wiring system with NYM-O 2x1,5 mm² (H07V-K
2x1,5mm²) cable with a maximum external diameter of 8 mm.
• The recuperator may not be used for the purpose of pumping of air containing:
- viscous contaminants, which may settle on the device,
- caustic contaminants, which may have an adverse in uence on the device,
- contaminants of mixtures of combustible substances in the forms of gases, steams, mists and dusts, which,
mixed with air, may form an explosive atmosphere.
• Control system may not allow extreme works including frequent activations and shutdowns.
• The device should be mounted in an external partition / wall, in an adequate distance from the sources of
contaminants (chimneys, ue gases etc.) so that exhausted / supplied air is free from contaminants.
EN