Ex-PM E
When configuring the ET 200SP HA and the ET 200SP, you must observe the
permissible number of I/O modules (see the respective operating instructions).
WARNING
Permissible number of I/O modules
When configuring the ET 200SP HA and the ET 200SP, you must observe the rules
specified below for the maximum configuration and load of the Ex power modules.
Load on the Ex power modules
Ensure that the current consumption of the Ex I/O modules of an Ex module group
does not exceed the permissible output current of the Ex power module.
The maximum current requirement of the I/O module can be found in the
technical specifications.
Permissible output current of the Ex power module > ∑ I
of the respective potential group
Commissioning
You must observe the national regulations during commissioning.
You must observe the guidelines according to DIN EN IEC 60079-17 for functional
checks.
Derating
The table shows the maximum permissible output current for the Ex-Power Module
depending on the installation position and the ambient temperature.
Mounting position
Horizontal installation
Vertical installation
Commissioning
You must observe the national regulations during commissioning.
You must observe the guidelines according to DIN EN IEC 60079-17 for functional
checks.
12
Ambient temperature
From -40 °C to 60 °C
From -40 °C to 70 °C
From -40 °C to 50 °C
From -40 °C to 60 °C
of all I/O modules
max
Output current
0.8 A
0.6 A
0.8 A
0.6 A
Ex-PM E

Werbung

loading

Diese Anleitung auch für:

Simatic et 200spEx-pm e